Site Preparation and Installation

21

Figure 13 Indoor air-cooled centrifugal condensing unit dimensions and pipe connections

7/8" (22mm) & 1 1/8" (29mm)
dia. knockouts electrical entrance

for high voltage connection

Air Outlet

7/8" (22.2mm) dia. electrical entrance
for low voltage connection.

7/8" (22.2mm) dia. knockout
electrical entrance for alternate
control panel low voltage routing.

Air Inlet

Single Point Power Kit
connection from Evaporator.

40 5/32 "

8 13/16 "

19 1/32 "

CABINET

DIMENSION

66 9/32 "

59 13/16 "

CABINET

DIMENSION

23 7/8 "

64 1/4 "

42 17/32 "

Shaded area indicates a
recommended clearance of
30" (762mm)

for component

access and removal.

Hanger
Bracket

Customer supplied
threaded rods for module
support from ceiling (1/2"
minimum diameter
recommended) (typ. 4).

NOTE: Unit is spaced evenly in
reference to threaded
rod centers.

9/16" (14mm) dia. holes for
threaded rods (typ. 2 each end)

1 3/32 "

16 5/16 "

26 3/8 "

1 13/16 "

(1683.5mm)

(1020mm)

(40mm)

(1519mm)

(483mm)

(224mm)

(26mm)

(414mm)

(670mm)

(606mm)

(1080.3mm)

(1632mm)

THREADED ROD

CENTERS

THREADED ROD

CENTERS

13/16"

(21mm)

System 1 (3Ton) Suction Line Connection,
Aeroquip #11 Male.

System 2 (5Ton) Suction Line Connection,
Aeroquip #12 Male.

System 1 (3Ton) Liquid Line Connection,
Aeroquip #6 Male.

System 2 (5Ton) Liquid Line Connection,
Aeroquip #10 Male.

DPN000248_Rev1