Setup Options

Access to setup options is restricted to three System Setup Levels: 0, 1,
or 2. The higher the level, the more setup options are available. Options
on System Setup Level 0 do not require password access.

Table 9. Setup Options

Minimum

Level*

Description

Available Settings

Default Setting

0

Enter Password

Use the arrow keys to enter the password for the level you
want to access, then select DONE to display the options for
the setup level

Level 1: L1
Level 2: Contact your
service representative

0

Versions

Read only

Current firmware
versions installed

0

Contrast Adjust

Adjust screen contrast with left/right arrow buttons

10%

1

Log Out

Exit the Level 1 or Level 2 setup options and display the
Level 0 setup options

None

1

Change Access
Level Password

Change the password for the current setup level
Use the arrow keys to enter the new password (A–Z, 0–9, –,
blank,), then select DONE to save the new password.

None

1

Set Date and Time

Set Month, Date, Year (mm/dd/yyyy)
Set Hour, Minute (Time is a 24−hour clock.)

00/00/0000
00:00

1

Clear History

Clear the History Log

None

1

Clear Load Profile

Clear the Load Profile

None

1

Building Alarm
Setup
(see page 53)

For Building Alarm 1 through Building Alarm 4:
Name String [up to 19 characters (A–Z, 0–9, –, blank)]
Settings: Contact Normally Open or Closed

Building Alarm Type (REPO, EPO, TVSS/SPD,

Custom)

Notice Level (Log and Alarm options)

Enabled/Disabled

BUILDING ALARM [X]
Open
1 and 2: Custom;
3: REPO; 4: EPO
Log Only
Enabled

1

THD Alarm Level

Set the voltage and current Total Harmonic Distortion for
Input 1 and Input 2, and enable or disable this feature:
THD settings
Enabled/Disabled

5.0
Disabled

2

Unit Type

Read only: Model / CTO / Serial

Factory−set identifiers

2

Unit Name

Up to 19 characters (A–Z, 0–9, –, blank)

EATON EMS−UGK

2

Reset All Lower
Level Passwords

Reset the Level 1 password to the default setting

None

* Minimum System Setup Level required to access the setup option.