Configuring panels containing subfeed breakers – Powerware 208/120V User Manual

Page 50

Advertising
background image

OPERATION

EATON Powerware

®

Energy Management System (EMS) Upgrade Kit User’s Guide

S

164201724 Rev 1

www.powerware.com

44

4.

On the PANEL CONFIG screen, set the panel’s meter settings:

Default

Range

Meter Setting

Description

3

3

PHASES

Number of phases

42

0–42
(even numbers)

BREAKERS

Number of branch circuit
breakers in the panel

100

0–1200

RATING

Panel breaker rating (in amps)
(see Note 1)

STANDARD

STANDARD
COLUMN

PNL LAYOUT

Panel layout
(see Note 2)

NOTE 1 Setting the panel breaker rating to 0 silences all main panel breaker
alarms and zeroes the panel percent current levels.
NOTE 2 Changing panel layout erases all branch circuit breaker configurations.

To reset all values on the screen to defaults, set the RESET value to
YES.

5.

Select OK.

6.

Repeat Steps 3 to 5 for each panel containing branch circuit
breakers to configure.

7.

When all panel configuration is complete, select the

button

repeatedly to reach the main menu.

8.

If all configuration is complete, save your changes by pressing the
Reset button on the Power Xpert Gateway Card in the X−Slot
communication bay. (The card automatically resets after five
minutes.) Otherwise, continue to Configuring Branch Circuit
Breakers" on page 46.

Configuring Panels Containing Subfeed Breakers

To configure panels containing subfeed breakers (up to 12 per panel):

1.

If not already obtained, access the System Setup Level 1 password
level. See Accessing Configuration" on page 43.

2.

From the main menu, select METER then PANEL.

3.

On the PANEL screen, select the panel number (PNL) to configure,
and then select CONFIG.