COMMUNICATION

EATON Powerware

®

Energy Management System (EMS) Upgrade Kit User’s Guide

S

164201724 Rev 1

www.powerware.com

52

Control Terminals

The cables should be connected to the control terminals with a mating
connector. The relay contact terminals have functional electrical isolation
from the system. The building alarms share a common (–) through
100 ohms, and have functional electrical isolation from the system, but
not from each other.

+ Polarity

– Polarity

1

+ Polarity

– Polarity

2

Building Alarm 1

Building Alarm 2

Normally Closed

Normally Open

NC

NO

Common

C

Relay Output

EMS−UGK
Connectors
(see Figure 20 on
page 49)

+ Polarity

– Polarity

4

Building Alarm 4

+ Polarity

– Polarity

3

Building Alarm 3

TB1

TB2

Figure 22. External Control Terminal Connections

NOTE If using a semiconductor switch type, pay attention to the proper polarity. A relay or
other contact closure is preferred.