◊ In the light and medium modes (one and two drops in the display) the Y2

valve will be energized until the bypass probe (B5) is satisfied.

◊ In the full mode (3 drops in the display) the Y2 valve will be energized

continuously.

g

When the timer counts to 0 or the core temp probe (B10) reaches the set amount

the cycle ends.

7

With the combi in the Rethermalization mode with time on the timer, the door closed

and the start switch is depressed
a

The front display will include a lighted bar under the Rethermalization symbol

• When the heat circuit is energized the heat symbol will be energized

• The cooking mode symbol will be energized.

• The time display will invert and begin to count down.

b

The fan circuit is energized

• If the combi fan is in the normal setting 220 VAC is sent from terminal 5 on

connector X11 through the normally closed auxiliary contacts of contactor
K57 to the coils of contactors K55 and K56
◊ The K55 and K56 contactors close sending 220 VAC through the Q56

overload to the motor and the motor turns at a high speed.

◊ The normally closed auxiliary contacts of both K55 and K56 open

preventing the K57 contactor from energizing.

• If the combi fan is in the reduced setting 220 VAC is sent from terminal 6 on

connector X11 through the normally closed auxiliary contacts of contactors
K55 and K56 to the coil of contactor K57
◊ The K57 contactor closes Sending 220 VAC through the Q57 thermal

overload to the motor and the motor turns at a reduced speed.

◊ The normally closed auxiliary contacts of K57 open preventing the K55

and K56 contactors from energizing.

• For the first 2 minutes 220 VAC is sent from terminal 4 on connector X11

through the normally closed auxiliary contacts of contactor K5 to the K50
contactor coil
◊ K50 contactor closes and the motor turns CW

◊ The normally closed auxiliary contacts on K50 open preventing the K5

contactor from energizing.

• For 15 seconds the motor is de-energized and allowed to coast.

• For the next 2 minutes 220 VAC is sent from terminal 3 on connector X11

through the normally closed auxiliary contacts of contactor K50 to the K5
contactor coil
◊ K5 contactor closes and the motor turns CCW

◊ The normally closed auxiliary contacts on K5 open preventing the K50

contactor from energizing.

NOTE: If the door switch (S7) opens by the door opening, then the fan circuit

is de-energized. Then the motor will be pulsed in the opposite direction to
“break” the fan. This is to stop the fan quicker for the operator.

c

The hot air heat circuit is energized

82