Majestic fireplaces, Nvb series b-vent, Venting runs – Majestic Appliances NVBC36 User Manual

Page 11

Advertising
background image

11

Majestic Fireplaces

®

NVB Series B-Vent

7412950

FP567

Fig. 13 Venting configurations.

Venting Runs

40

38

36

34

32

30

28

26

24

22

20

18

16

14

12

8 9 10

1 2 3 4 5 6 7

Horizontal Run (in feet)

Ve

rtical Run (in feet)

A

A: Vertical installations up to 40 feet (12m) in
height. Up to a 6 ft. horizontal vent run can be
installed within the vent system using a
maximum of two 90-degree elbows or four
45-degree elbows.

B: Vertical installations up to 40 feet (12m) in
height. Up to a 10 ft. horizontal vent run can be
installed within the vent system using a
maximum of two 45-degree elbows.

B

= Acceptable venting configuration

= Unacceptable venting configuration

FP567a

Fig. 14 Venting configurations when installing 36GSKBB.

40

38

36

34

32

30

28

26

24

22

20

18

16

14

12

10

8

2

4

6

8

10 12 14 16 18

20

A

Horizontal Run (in feet)

V

ertical Run (in feet)

= Acceptable venting configuration

= Unacceptable venting configuration

A: Vertical installation up to 40 feet (12m) in
height. Up to a 16 ft. horizontal vent run
can be installed within the vent system
using a maximum of two 90 degree elbows
or four 45 degree elbows.

B: Vertical installation up to 40 feet (12m) in
height. Up to a 20 ft. horizontal vent run
can be installed within the vent system
using a maximum of two 45 degree elbows.

B