Setting for interval, Setting for reference voltage – KYORITSU 6310 Instruction Manual User Manual
Page 79
4.2.2 Measurement Setting (QUALITY-Swell, Dip, INT Measurement) KEW6310
KEW6310
4.38
Setting for interval
Interval is a space of the time between data savings; data is saved in a CF card or Internal memory.
* Default value (or after system reset) : 30 min
* Setting procedure is same to that for interval Setting for W/ Wh/ DEMAND.Refer to the procedure described in
the preceding pages.
Setting for reference voltage
70 ~ 1000V (can be set by 1V)
* Default value (or after system reset) : 100V
1
Press the
Cursor
Keys and select [V_Reference], and then press the
ENTER
Key.
2
Press the
Cursor
Keys and alter values, and then press the
ENTER
Key.
Box with
▲▼
mark appears
at the rightmost digit.
Selected reference voltage
is displayed.