Logic connections, Operational settings – Basler Electric BE1-11g User Manual

Page 138

Advertising
background image

126

9424200994 Rev N

Logic Connections

Power element logic connections are made on the BESTlogicPlus screen in BESTCOMSPlus. The power
element logic block is illustrated in Figure 78. Logic inputs and outputs are summarized in Table 44.

Figure 78. Power Element Logic Block

Table 44. Logic Inputs and Outputs

Name

Logic Function

Purpose

Block

Input

Disables the 32 function when true

Trip

Output

True when the 32 element is in a trip condition

Pickup

Output

True when the 32 element is in a pickup condition

Operational Settings

Power element operational settings are configured on the Power (32) settings screen (Figure 79) in
BESTCOMSPlus. Setting ranges and defaults are summarized in Table 45.

Figure 79. Power Settings Screen

Table 45. Operational Settings

Setting

Range

Increment

Unit of

Measure

Default

Mode

Disabled, One of Three, Two of Three, Three

of Three, or Total Power

n/a

n/a

Disabled

Pickup

0 or 1 to 6,000 (5A CTs)
0 or 1 to 1,200 (1A CTs)

varies

watts

0

Time

Delay

0 or 50 to 600,000

varies

milliseconds

0

Direction

Forward or Reverse

n/a

n/a

Forward

Over

Under

Over or Under

n/a

n/a

Over

Power (32) Protection

BE1-11g