Voltage, Distortion, Dip/swell – Basler Electric BE1-11g User Manual

Page 238

Advertising
background image

226

9424200994 Rev N

Voltage

Figure 159 illustrates the Power Quality, Voltage screen.

Figure 159. Power Quality, Voltage Screen

10-Second Frequency

A 10-second average of the frequency is calculated using Equation 24.

π‘π‘’π‘šπ‘π‘’π‘Ÿ π‘œπ‘“ πΌπ‘›π‘‘π‘’π‘”π‘Ÿπ‘Žπ‘™ 𝐢𝑦𝑐𝑙𝑒𝑠

π‘‡π‘œπ‘‘π‘Žπ‘™ π·π‘’π‘Ÿπ‘Žπ‘‘π‘–π‘œπ‘› π‘œπ‘“ πΌπ‘›π‘‘π‘’π‘”π‘’π‘Ÿ 𝐢𝑦𝑐𝑙𝑒𝑠

Equation 24. 10-Second Frequency Calculation

Example

Number of integral cycles: 501 cycles over 10 s

Total duration of the 501 cycles: 9.998 s

10-Second Frequency = 501/9.998 = 50.1100 Hz

Distortion

The voltage during a dip is often distorted. This distortion may be important for understanding the effect of
the dip on the system. The BE1-11g calculates distortion using Equation 25.

οΏ½

𝑉

π‘‡π‘œπ‘‘π‘Žπ‘™

𝑉

πΉπ‘’π‘›π‘‘π‘Žπ‘šπ‘’π‘›π‘‘π‘Žπ‘™

βˆ’ 1οΏ½ Γ— 100

Equation 25. Distortion Calculation

Figure 160 illustrates the Power Quality, Distortion screen.

Figure 160. Power Quality, Distortion Screen

Dip/Swell

Figure 161 illustrates the Power Quality, Dip/Swell screen. A green LED indicates that the threshold
specified in Power Quality Settings has been exceeded.

Power Quality

BE1-11g

Advertising