Figure 387. RTD Type Selection Screen

Use the Settings Explorer to open the Programmable Outputs, Remote RTD, RTD Block Configuration
tree branch and enter a user-defined name (up to 64 alphanumeric characters) for the RTD Configuration
Block selected. Check the boxes next to the RTDs to include in each configuration group. See Figure 388.

The source for the 49RTD protection elements can be set for RTD Group 1, 2, 3, 4, 5, 6, or 7. Refer to the

Resistance Temperature Detector (49RTD) Protection

chapter for information on setting 49RTD

protection elements.

Figure 388. RTD Configuration Block Screen

Specifications

Operating Power

Nominal ...................................... 125/250 Vac/dc
Range ......................................... 90 to 270 Vac or 90 to 300 Vdc
Maximum Consumption ............. 9 W

Analog Inputs

The RTD module contains four programmable analog inputs.
Rating ......................................... 4 to 20 mAdc or 0 to 10 Vdc (user-selectable)

RTD Inputs

The RTD module contains 12 programmable RTD inputs.
User-Selectable Types ............... 100

Ω Platinum (DIN43760), 10 Ω Copper, 100 Ω Nickel, or 120 Ω Nickel

Range .........................................

–50 to 250°C (–58 to 482°F)

Accuracy.....................................

±2°C (3.6°F)