Electrical wiring, Caution, Warning – Goodman Mfg IO-354B User Manual

Page 8

Advertising
background image

8

T

O

PREVENT

SEVERE

DAMAGE

TO

THE

BOTTOM

OF

THE

UNIT

,

DO

NOT

FORK

LIFT

UNIT

AFTER

WOOD

STRUTS

HAVE

BEEN

REMOVED

.

CAUTION

Bring condenser end of unit into alignment with the curb. With
condenser end of the unit resting on curb member and using
curb as a fulcrum, lower opposite end of the unit until entire
unit is seated on the curb. When a rectangular cantilever
curb is used, care should be taken to center the unit. Check
for proper alignment and orientation of supply and return open-
ings with duct.

R

IGGING

R

EMOVAL

T

O

PREVENT

DAMAGE

TO

THE

UNIT

,

DO

NOT

ALLOW

CRANE

HOOKS

AND

SPREADER

BARS

TO

REST

ON

THE

ROOF

OF

THE

UNIT

.

CAUTION

Remove spreader bars, lifting cables and other rigging equip-
ment.

ELECTRICAL WIRING

HIGH VOLTAGE!
D

ISCONNECT

ALL

POWER

BEFORE

SERVICING

OR

INSTALLING

THIS

UNIT

. M

ULTIPLE

POWER

SOURCES

MAY

BE

PRESENT

. F

AILURE

TO

DO

SO

MAY

CAUSE

PROPERTY

DAMAGE

,

PERSONAL

INJURY

OR

DEATH

.

WARNING

HIGH VOLTAGE!
T

O

AVOID

PERSONAL

INJURY

OR

DEATH

DUE

TO

ELECTRICAL

SHOCK

,

DO

NOT

TAMPER

WITH

FACTORY

WIRING

. T

HE

INTERNAL

POWER

AND

CONTROL

WIRING

OF

THESE

UNITS

ARE

FACTORY

-

INSTALLED

AND

HAVE

BEEN

THOROUGHLY

TESTED

PRIOR

TO

SHIPMENT

.

C

ONTACT

YOUR

LOCAL

REPRESENTATIVE

IF

ASSISTANCE

IS

REQUIRED

.

WARNING

T

O

PREVENT

DAMAGE

TO

THE

WIRING

,

PROTECT

WIRING

FROM

SHARP

EDGES

. F

OLLOW

NATIONAL

ELECTRICAL

CODE

AND

ALL

LOCAL

CODES

AND

ORDINANCES

. D

O

NOT

ROUTE

WIRES

THROUGH

REMOVABLE

ACCESS

PANELS

.

CAUTION

C

ONDUIT

AND

FITTINGS

MUST

BE

WEATHER

-

TIGHT

TO

PREVENT

WATER

ENTRY

INTO

THE

BUILDING

.

CAUTION

For unit protection, use a fuse or HACR circuit breaker that is
in excess of the circuit ampacity, but less than or equal to the
maximum overcurrent protection device. DO NOT EXCEED
THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN
ON UNIT DATA PLATE.

All line voltage connections must be made through weather-
proof fittings. All exterior power supply and ground wiring
must be in approved weatherproof conduit.

The main power supply wiring to the unit and low voltage
wiring to accessory controls must be done in accordance with
these instructions, the latest edition of the National Electrical
Code (ANSI/NFPA 70), and all local codes and ordinances.
All field wiring shall conform with the temperature limitations
for Type T wire (63°F/35°C rise).

The unit is factory wired for the voltage shown on the unit’s
data plate. Refer to model nomenclature in Appendix D for
voltage requirement for your unit.

NOTE: If supply voltage is 208V, lead on primary of trans-
former must be moved from the 230V to the 208V tap. Refer
to wiring diagram on unit for details.

Main power wiring should be sized for the minimum wire
ampacity shown on the unit’s data plate. Size wires in accor-
dance with the ampacity tables in Article 310 of the National
Electrical Code. If long wires are required, it may be neces-
sary to increase the wire size to prevent excessive voltage
drop. Wires should be sized for a maximum of 3% voltage
drop.

CAUTION

T

O AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USE

ONLY COPPER CONDUCTORS.

L

ABEL

ALL

WIRES

PRIOR

TO

DISCONNECTION

WHEN

SERVICING

CONTROLS

. W

IRING

ERRORS

CAN

CAUSE

IMPROPER

AND

DANGEROUS

OPERATION

. V

ERIFY

PROPER

OPERATION

AFTER

SERVICING

.

CAUTION

NOTE: A weather-tight disconnect switch, properly sized for
the unit total load, must be field installed. An external field
supplied disconnect may be mounted on the exterior panel.

Ensure the data plate is not covered by the field-supplied
disconnect switch.

Some disconnect switches are not fused. Protect the
power leads at the point of distribution in accordance
with the unit’s data plate.

The unit must be electrically grounded in accordance
with local codes or, in the absence of local codes,
with the latest edition of the National Electrical Code
(ANSI-NFPA 70). A ground lug is provided for this
purpose. Size grounding conductor in accordance
with Table 250-95 of the National Electrical Code. Do
not use the ground lug for connecting a neutral
conductor.

Remove plug in panel located at the condenser end
of unit and route conduit to control box. Remove plug
in control box and connect power wiring to the
contactor closest to the entrance. If Single Point kit is
used, refer to Installation Instructions supplied with
kit.