Air Output, Air Intake,
and Lint Filters

1. Remove upper shell (see

page 10).

2. Remove filter end cover

screws using 5/16" nut-
driver.

3. Remove filter end cover.
4. Replace air output and lint

filters.

5. Wash or replace air intake

filter (see Preventative
Maintenance Schedule,
page 8).

6. Replace filter end cover.
7. Replace fan guard and

upper shell.

IMPORTANT:

Do not oil

filters

Air Intake Filter

Lint Filter

Filter End
Cover

Air Output
Filter

Fan Guard

Figure 20 - Air Output, Air Intake, and Lint Filters,

30/70,000 BTU/Hr Models

Air Intake Filter

Filter End
Cover

Lint Filter

Air Output
Filter

Figure 21 - Air Output, Air Intake, and Lint Filters,

90/150,000 BTU/Hr Models

PRESSURE GAUGE PLUG

PFA/OV 006B

Figure 22 - Pressure Gauge Plug Removal

Pressure
Gauge
Plug

Pressure
Gauge

Figure 23 - Adjusting Pump Pressure

Pump

Model

Pressure

30,000 BTU/Hr

2.6 PSI

70,000 BTU/Hr

3.8 PSI

90,000 BTU/Hr

4.4 PSI

150,000 BTU/Hr

4.9 PSI

(30/70,000 BTU/Hr Models Shown)

Relief
Valve

Fan Guard
(90,000 BTU/Hr
Model Shown)

Pump Pressure
Adjustment

1. Remove pressure gauge

plug from filter end cover.

2. Install accessory pressure

gauge (part number
HA1180).

3. Start heater (see Operation,

page 7). Allow motor to
reach full speed.

4. Adjust pressure. Turn relief

valve to right to increase
pressure. Turn relief valve
to left to decrease pressure.
See specifications at right
for correct pressure for
each model.

5. Remove pressure gauge.

Replace pressure gauge
plug in filter end cover.