1.5.3 Hidden Panel Indicators

The hidden panel is located behind the hinged cover, at the lowest pane of the front panel, refer to Figure 1-8.

The hidden panel includes the alphanumeric display and controls, and following controls and indicators, see Figure 1-

11.

Figure 1-11: Hidden Panel Alphanumeric LEDs and Pushbutton Indicators and Controls.

Hidden panel alphanumeric legend: (upper display, details on following page)

A

Emergency Shutdown

G

Battery charging

L

Overload

B

Rectifier/Charger on

H

Inverter fault

M

Bypass outside tolerance

C

Rectifier/Charger fault

I

Battery discharged

N

Maintenance position

D

Input Outside Tolerance

J

Inverter Desynchronized

F

Battery temp. outside Tolerance

K

Transfer Fault

(lower display)

(port) Test connector

fault Clear faults

(audio)

Alarm reset

1

Battery charge cycle

2

Return to float voltage

(key)

Security

3

Inverter sync/desync

4

Forced Transfer

5

Forced Shutdown

1.5.3.1 LED Alphanumeric Indicators

Fourteen alphabetically labeled LEDs provide detailed information on UPS status as follows:

A: Emergency shutdown

This red LED indicates that the emergency power off (EPO) or remote emergency power off (REPO) has been

activated. See section 2.10.1, Emergency power off.

B: Rectifier/charger on

This green LED indicates that the rectifier/battery charger is on.