Startup – IBM Uninterruptible Power Supply IBM UPS 7500XHV User Manual

Page 13

Advertising
background image

9

Connecting Equipment and Power to the Rear Panel of the Uninterruptible Power Supply

INDEX ITEM

DESCRIPTION

1

Outlets

Connect equipment to the uninterruptible power supply.

2

Output Circuit Breakers

Each circuit breaker protects its nearest outlet.

3

EPO Terminal

The optional Emergency Power Off (EPO) feature enables connected
loads to be immediately de-energized from a remote location, without
switching to battery operation. See Emergency Power Off (EPO) Option.

4

Bypass Switch

This switch will put the unit in bypass mode. See Operation.

5

Serial Port

Power management software and serial port communication can be used
with the uninterruptible power supply. Use only cables supplied or ap-
proved by IBM.
Note: Use the supplied serial cable to connect to the serial port. Do not
use a standard serial interface cable because it is incompatible with the
uninterruptible power supply connector.

6

Integrated Environmental
Monitor

This Network Management Card monitor features a tempera-
ture/humidity probe, two input contacts, and a two-position output relay.
For information on connecting and using the probes, contacts, and relay,
see the Network Management Card CD.

7

Input Circuit Breaker

The uninterruptible power supply is protected from extreme overloads when in
the on position.

The breaker must be on for the unit to operate.

8 Ethernet

Port/

Network

Management Card

Connect the uninterruptible power supply to the network.

9

Battery Pack Connectors

Optional battery packs provide extended runtime during power outages.
See 3U Extend Run Battery Pack Operation and Setup Guide.

10

Access Panel

Provides access to the terminal blocks. See Hardwiring the Uninterrupti-
ble Power Supply.

11

TVSS Screw

The uninterruptible power supply features a transient voltage surge-
suppression (TVSS) screw for connecting the ground lead on surge sup-
pression devices such as telephone and network line protectors. When
connecting a grounding cable, disconnect the uninterruptible power sup-
ply from the utility power outlet.

Startup

1. Hardwire the uninterruptible power supply. See Hardwiring the Uninterruptible Power Supply.

2. Connect equipment to the uninterruptible power supply.

3. Turn on all connected equipment. To use the uninterruptible power supply as a master on/off switch, be sure all connected

equipment is turned on.

4. Press the

button on the front panel to turn on the uninterruptible power supply.

5. Select the ouput voltage (default is 230 V). See Setting the Output Voltage via Terminal Mode.

Note: For setting the number of external battery packs through Terminal Mode, see the 3U Extend Run Battery Pack Op-
eration and Setup Guide.

6. Configure the Network Management Card (optional).