ICP DAS USA 8KE8 User Manual

Page 75

Advertising
background image

$AASi6

Command $AASi6
Description Read back the Digital Output module value and read the Digital Input

module value of a specified slot in the I-8000 unit.
$AASi6[CHK](cr)
$

A delimiter character

AA

A 2-character HEX module address for the specified
I-8000 unit, ranging from 01 to FFh

Si

The specified slot number. i = 0 to 3 (4 slots) or
i = 0 to 7 (8 slots)

6

A Command to read the data

[CHK] A

2-character

checksum

Syntax

(cr)

Carriage Return (0x0D) to denote the end of
command

Valid Command

!0D0E00[CHK](cr) for 8-bit DIO modules
!DD0000[CHK](cr) for 8-bit (or less than 8 bits)
DO modules
!EE0000[CHK](cr) for 8-bit (or less than 8 bits) DI
modules
!DDEE00[CHK](cr) for 16-bit DIO modules
!DDDD00[CHK](cr) for 16-bit DO modules
!EEEE00[CHK](cr) for 16-bit DI modules
!DDDDEEEE[CHK](cr) for 32-bit DIO modules
!DDDDDDDD[CHK](cr) for 32-bit DO modules
!EEEEEEEE[CHK](cr) for 32-bit DI modules

Invalid Command

?AA[CHK](cr)

Any syntax or communication error may receive no response.
!

A delimiter for valid command

?

A delimiter for invalid command

D

4-bit output value (0~Fh)

E

4-bit input value (0~Fh)

DD

8-bit output value (00~FFh)

EE

8-bit input value (00~FFh)

DDDD

16-bit output value (0000~FFFFh)

EEEE

16-bit input value (0000~FFFFh)

DDDDDDDD 32-bit

output

value (00000000~FFFFFFFFh)

EEEEEEEE

32 bit input value (00000000~FFFFFFFFh)

[CHK] A

2-character

checksum

(cr)

Carriage Return (0x0D) to denote the end of
response

Command $01S16
Response !0155AA00

Example

Description

The example reads the digital I/O module value from
slot 1 of the I-8000 unit at address 01h. The second
2-character value 55h (01010101) indicate the I/O
module channels 1,3,5,7 are ON and channels
0,2,4,6 are OFF.

8430/8830/8KE4/8KE8 User’s manual, Jan 2005, Version 1.0, 8MS-002-10 ----- 75

Advertising
This manual is related to the following products: