M9220-GGx-3 Proportional Electric Spring Return Actuators Installation Instructions

12

Cycles

60,000 Full Stroke Cycles; 1,500,000 Repositions

Audible Noise Rating

Power On
(Running)

<45 dBA at 39-13/32 in. (1 m)

Power On
(Holding)

<20 dBA at 39-13/32 in. (1 m)

Power Off
(Spring
Returning)

<55 dBA at 39-13/32 in. (1 m)

Electrical Connections

Actuator
(All Models)

48 in. (1.2 m) Halogen-Free Cable with 18 AWG (0.75 mm

2

) Wire Leads

Auxiliary
Switches
(GGC Models)

48 in. (1.2 m) Halogen-Free Cable with 18 AWG (0.75 mm

2

) Wire Leads

Conduit Connections

Integral Connectors for 3/8 in. (10 mm) Flexible Metal Conduit

Mechanical Connections

Standard
Shaft Clamp
Included with
Actuator

1/2 to 3/4 in. or 12 to 19 mm Diameter Round Shafts, or
3/8 and 1/2 in. or 10, 12, and 14 mm Square Shafts

Optional
M9220-600
Jackshaft
Coupler Kit

3/4 to 1-1/16 in. or 19 to 27 mm Diameter Round Shafts, or
5/8 and 3/4 in. or 16, 18, and 19 mm Square Shafts

Aluminum Enclosure

NEMA 2 (IP54) for All Mounting Orientations

Ambient Conditions

Operating

-40 to 131°F (-40 to 55°C); 90% RH Maximum, Noncondensing

Storage

-85 to 185°F (-65 to 85°C); 95% RH Maximum, Noncondensing

Dimensions

See Figure 1.

Compliance

United States

UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1,
Automatic Electrical Controls for Household and Similar Use; and
UL 60730-2-14: 2002-02, Ed. 1, Part 2, Particular Requirements for
Electric Actuators. (Models: All)

Canada

UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA:
July 2002, 3rd Ed., Automatic Electrical Controls for Household and
Similar Use; and CSA C22.2 No. 24-93 Temperature Indicating and
Regulating Equipment (Models: All).

Europe

CE Mark – Johnson Controls, Inc., declares that this product is in
compliance with the essential requirements and other relevant provisions
of the EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC.

Australia and
New Zealand

C-Tick Mark, Australia/NZ Emissions Compliant (Models: All)

Shipping Weight

6.4 lb (2.9 kg)

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.