TABLE 19: SUPPLY AIR BLOWER PERFORMANCE (BQ036 BELT DRIVE) - SIDE DUCT APPLICATION

Air

Flow

(CFM)

Available External Static Pressure - IWG

1

1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive

Standard Drive Option

HIgh Static Drive Option

800

678

0.37

761

0.44

840

0.52

917

0.60

991

0.69

1062

0.77

1130

0.87

1195

0.96

1259

1.06

1320

1.17

1000

699

0.42

782

0.49

862

0.56

939

0.64

1012

0.73

1083

0.82

1151

0.91

1217

1.01

1280

1.11

1341

1.21

1200

727

0.45

810

0.52

889

0.60

966

0.68

1040

0.76

1110

0.85

1179

0.95

1244

1.04

1308

1.14

1369

1.24

1400

759

0.51

842

0.58

922

0.65

998

0.73

1072

0.82

1143

0.91

1211

1.00

1276

1.10

1340

1.20

1401

1.30

1600

795

0.60

878

0.67

958

0.74

1035

0.82

1108

0.91

1179

1.00

1247

1.09

1313

1.19

1376

1.28

1438

1.39

FS

4

TABLE 20: SUPPLY AIR BLOWER PERFORMANCE (BQ036 BELT DRIVE) - BOTTOM DUCT APPLICATION

Air

Flow

(CFM)

Available External Static Pressure - IWG

1

1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive

Standard Drive Option

HIgh Static Drive Option

800

661

0.39

751

0.45

838

0.53

922

0.61

1002

0.69

1079

0.78

1153

0.87

1225

0.96

1294

1.06

1361

1.16

1000

685

0.43

775

0.50

862

0.57

945

0.65

1025

0.73

1103

0.82

1177

0.91

1248

1.00

1317

1.10

1384

1.20

1200

714

0.46

805

0.53

892

0.60

975

0.68

1055

0.76

1132

0.85

1207

0.94

1278

1.04

1347

1.13

1414

1.23

1400

749

0.52

840

0.58

927

0.66

1010

0.74

1090

0.82

1167

0.91

1242

1.00

1313

1.09

1382

1.19

1449

1.29

1600

789

0.60

880

0.67

967

0.74

1050

0.82

1130

0.91

1207

0.99

1282

1.08

1353

1.18

1422

1.27

1489

1.37

Field Supplied Drive

TABLE 21: SUPPLY AIR BLOWER PERFORMANCE (BQ048 BELT DRIVE) - SIDE DUCT APPLICATION

Air

Flow

(CFM)

Available External Static Pressure - IWG

1

1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive

Standard Drive Option

HIgh Static Drive Option

1000

656

0.41

757

0.46

851

0.52

937

0.58

1017

0.66

1092

0.73

1162

0.81

1228

0.90

1291

0.99

1351

1.08

1200

680

0.47

781

0.52

874

0.58

960

0.65

1041

0.72

1115

0.80

1185

0.88

1251

0.96

1314

1.05

1375

1.14

1400

706

0.56

807

0.61

901

0.67

987

0.73

1067

0.80

1142

0.88

1212

0.96

1278

1.05

1341

1.13

1401

1.22

1600

737

0.67

839

0.72

932

0.77

1018

0.84

1098

0.91

1173

0.99

1243

1.07

1309

1.15

1372

1.24

1433

1.33

1800

774

0.80

875

0.85

968

0.90

1055

0.97

1135

1.04

1209

1.12

1279

1.20

1345

1.28

1408

1.37

1469

1.46

2000

815

0.95

916

1.00

1010

1.06

1096

1.12

1176

1.19

1251

1.27

1321

1.35

1387

1.44

1450

1.52

1510

1.61

TABLE 22: SUPPLY AIR BLOWER PERFORMANCE (BQ048 BELT DRIVE) - BOTTOM DUCT APPLICATION

Air

Flow

(CFM)

Available External Static Pressure - IWG

1

1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive

Standard Drive Option

HIgh Static Drive Option

1000

638

0.42

748

0.47

849

0.53

944

0.59

1031

0.66

1112

0.74

1188

0.82

1260

0.90

1329

0.98

1395

1.07

1200

663

0.48

773

0.53

875

0.59

969

0.65

1056

0.72

1138

0.80

1214

0.88

1286

0.96

1354

1.04

1420

1.13

1400

692

0.57

802

0.61

904

0.67

998

0.73

1085

0.80

1167

0.88

1243

0.96

1315

1.04

1383

1.13

1449

1.21

1600

726

0.67

836

0.72

938

0.78

1032

0.84

1119

0.91

1201

0.98

1277

1.06

1349

1.15

1417

1.23

1483

1.32

1800

766

0.80

876

0.85

977

0.90

1072

0.97

1159

1.04

1240

1.11

1316

1.19

1388

1.27

1457

1.36

1523

1.45

2000

811

0.95

921

0.99

1023

1.05

1117

1.11

1204

1.18

1285

1.26

1362

1.34

1434

1.42

1502

1.51

1568

1.59

FS