Johnson Controls CM8M/CMLM*MP User Manual

Page 19

Advertising
background image

368261-UIM-A-0508

Johnson Controls Unitary Products

19

An unconfined space is not less than 50 cu.ft (1.42 m

3

) per 1,000 Btu/

hr (0.2928 kW) input rating for all of the appliances installed in that
area.

Rooms communicating directly with the space containing the appli-
ances are considered part of the unconfined space, if openings are fur-
nished with openings or louvers.

A confined space is an area with less than 50 cu.ft (1.42 m

3

) per 1,000

Btu/hr (0.2928 kW) input rating for all of the appliances installed in that
area. The following must be considered to obtain proper air for combus-
tion and ventilation in confined spaces.

Combustion Air Source From Outdoors

The blocking effects of louvers, grilles and screens must be given con-
sideration in calculating free area. If the free area of a specific louver or
grille is not known, refer to Table 7, to estimate free area.

* Do not use less than 1/4”(0.635 cm) mesh
+ Free area of louvers and grille varies widely; the installer should follow

louver or grille manufacturer’s instructions.

Dampers, Louvers and Grilles (Canada Only)

1.

The free area of a supply air opening shall be calculated by sub-
tracting the blockage area of all fixed louvers grilles or screens
from the gross area of the opening.

2.

Apertures in a fixed louver, a grille, or screen shall have no dimen-
sion smaller than 0.25” (0.64 cm).

3.

A manually operated damper or manually adjustable louvers are
not permitted for use.

4.

A automatically operated damper or automatically adjustable lou-
vers shall be interlocked so that the main burner cannot operate
unless either the damper or the louver is in the fully open position.

Air Supply Openings and Ducts

1.

An opening may be used in lieu of a duct to provide to provide the
outside air supply to an appliance unless otherwise permitted by
the authority having jurisdiction. The opening shall be located
within 12” (30.5 cm) horizontally from, the burner level of the appli-
ance. Refer to “COMBUSTION AIR SOURCE FROM OUTDOORS
and VENT AND SUPPLY AIR SAFETY CHECK” in these instruc-
tions for additional information and safety check procedure.

2.

The duct shall be either metal, or a material meeting the class 1
requirements of CAN4-S110 Standard for Air Ducts.

3.

The duct shall be least the same cross-sectional area as the free
area of the air supply inlet opening to which it connects.

4.

The duct shall terminate within 12 in (30.5 cm) above, and within
24 in (61 cm) horizontally from, the burner level of the appliance
having the largest input.

5.

A square or rectangular shaped duct shall only be used when the

required free area of the supply opening is 9 in

2

(58.06 cm

2

) or

larger. When a square or rectangular duct is used, its small dimen-
sionshall not be less than 3 in (7.6 cm).

6.

An air inlet supply from outdoors shall be equipped with a means
to prevent the direct entry of rain and wind. Such means shall not
reduce the required free area of the air supply opening.

7.

An air supply inlet opening from the outdoors shall be located not
less than 12” (30.5 cm) above the outside grade level.

Combustion Air Source from Outdoors

1.

Two permanent openings, one within 12 in (30.5 mm) of the top
and one within 12 in (30.5 mm) of bottom of the confined space,
Two permanent openings, shall communicate directly or by means
of ducts with the outdoors, crawl spaces or attic spaces.

Table 7: Estimated Free Area

Wood or Metal

Louvers or Grilles

Wood 20-25%*

Metal 60-70% *

Screens+

1/4” (0.635 cm)

mesh or larger 100%

When a Category I furnace is removed or replaced, the original
venting system may no longer be correctly sized to properly vent
the attached appliances.
An improperly sized vent system can cause CARBON MONOXIDE
to spill into the living space causing personal injury, and or death.

Table 8: Unconfined Space Minimum Area in Square Inch

BTUH Input Rating

Minimum Free Area in Square Feet

Required for Each Opening

60,000

60 (387 cm

2

)

80,000

80 (516 cm

2

)

100,000

100 (645 cm

2

)

120,000

120 (742 cm

2

)

Table 9: Free Area

BTUH Input

Rating

Minimum Free Area Required for Each Opening

Horizontal Duct

(2,000 BTUH)

Vertical Duct or

Opening to Outside

(4,000 BTUH)

Round Duct

(4,000 BTUH)

60,000

30 in

2

(193 cm

2

)

15 in

2

(97 cm

2

)

5” (13 cm)

80,000

40 in

2

(258 cm

2

)

20 in

2

(129 cm

2

)

5” (13 cm)

100,000

50 in

2

(322 cm

2

)

25 in

2

(161 cm

2

)

6” (15 cm)

120,000

60 in

2

(387 cm

2

)

30 in

2

(193 cm

2

)

7” (18 cm)

EXAMPLE: Determining Free Area.
Appliance

1 Appliance

2 Total Input

100,000

+ 30,000 = (130,000

÷ 4,000) = 32.5 Sq. In. Vertical

Appliance

1 Appliance

2 Total Input

100,000

+ 30,000 = (130,000

÷ 2,000) = 65 Sq. In. Horizontal

FIGURE 28: Outside and Ambient Combustion Air

Gable
Vent

Gas
Vent

Soffit
Vent

Ventilated

Attic

Top Above
Insulation

Optional
Inlet (a)

Outlet
Air (a)

Ventilated

Crawl Space

Gas
Water
Heater

Furnace

Soffit
Vent

Gas
Water
Heater

Inlet
Air (a)

Inlet
Air (b)

Furnace

Gas
Vent

Outlet
Air (a)

Outlet
Air (b)

Inlet
Air (a)

Inlet
Air (b)

Gas
Water
Heater

Furnace

Ventilated

Attic

Top Above
Insulation

Gable
Vent

Gas
Vent

Advertising
This manual is related to the following products: