Horizontal termination – Jotul GF100 DV User Manual

Page 10

Advertising
background image

10

Horizontal Termination

„

Wall Cut-out Opening: A minimum 10" X 10" (250 mm x
250 mm) square hole is required for proper pipe clear-
ances through a combustible wall. Use vent
manufacturer’s WALL THIMBLE for the wall penetration.

DO NOT FILL AIR SPACE WITH ANY TYPE OF INSULATION.

„

The minimum horizontal run made directly off the
rear of the stove into a standard horizontal cap shall
be no less than a 6” vent section. See fig. 8.

„

The maximum horizontal run made directly off the
rear of the stove into a standard horizontal cap (#984
or #985) must include no more than a 12” and 6”
section of Simpson Dura-Vent pipe installed together.
See fig.9.

„

The maximum horizontal run made directly off the
rear of the stove into a 14” snorkel cap must include
no more than a 24” vent section . See fig. 10.

„

The horizontal termination cap must maintain a 3"
clearance to any overhead combustible projections
2 1/2" or less. It must also maintain 12" clearance
from projections exceeding 2 1/2". See fig. 14.

„

Any horizontal run of vent must be level or have a
1/4" rise for every foot of run toward the termination
cap. NEVER ALLOW THE VENTING TO RUN DOWN-
WARD FROM STOVE TO TERMINATION; DOWNWARD
VENT RUNS TRAP HEAT AND CAUSE HIGH TEMPERA-
TURES TO DEVELOP WITHIN THE VENT THAT COULD
START A FIRE.

„

Install a Vinyl Siding Standoff between the vent
termination and an exterior wall covered by vinyl
siding material to prevent potential heat damage to
the siding.

„

Do not recess the termination cap into a wall or
siding.

Options for immediate horizontal venting
directly off the rear of the stove

Figure 8. Minimum Horizontal Run - Standard Termination.

Standard Horizontal

Termination Cap

Min. Horizontal: 6”

No draft restriction required.

5” min.

130 mm

WALL THIMBLE required.

12

12

12

12

12

12

12

12

12

12

Standard Horizontal

Termination Cap

Max. Horizontal Run:

12”

No draft restriction required.

17” Max.

430 mm

WALL THIMBLE required.

12

12

12

12

12

12

12

12

12

12

Figure 9. Maximum Horizontal Run - Standard
Termination.

WALL THIMBLE required.

14” Snorkel

Figure 10. Maximum Horizontal Run with Snorkel
Termination.

12

12

12

12

12

12

Max. Horizontal run into a 14”

snorkel: 24”

A draft restrictor is required.

24 3/4”

(630 mm)