The thermostat supports the following applications, which can be configured via
DIP switches
at the rear of the unit. The control output for the damper actuator is
either DC 0…10 V (factory setting) or 3-position (see parameter P47), and for the
heating / cooling output ON/OFF, PWM, 3-position or DC 0…10 V.

Application

DIP switch

Control output

DC 0…10 V

Single-duct

• DC 0…10 V damper actuator
• 3-position damper actuator

YV

T

B1

M

V

1 2 3 4 5

ON

OFF

3-position

DC 0…10 V

Single-duct with electrical heater

• DC 0…10 V damper actuator and

ON/OFF, PWM or 3-position electrical
heater

• 3-position damper actuator and

DC 0…10 V electrical heater

YV

YE

M

V

T

B1

1 2 3 4 5

ON

OFF

ON/OFF, PWM or
3-position

DC 0…10 V

Single-duct and radiator / floor
heating

• DC 0…10 V damper actuator and

ON/OFF, PWM or 3-position radiator

• 3-position damper actuator and

DC 0…10 V radiator

YR

YV

T

B1

1 2 3 4 5

ON

OFF

ON/OFF, PWM or
3-position

DC 0…10 V

Single-duct heating / cooling coil

• DC 0…10 V damper actuator and

ON/OFF, PWM or 3-position heating /
cooling

• 3-position damper actuator and

DC 0…10 V heating /cooling

YV

M

V

Y1

T

B2

T

B1

1 2 3 4 5

ON

OFF

ON/OFF, PWM or
3-position


Key

Y1 Heating or heating/cooling valve actuator B1 Return air temperature sensor or external

room temperature sensor (optional)

YV damper actuator

B2 Changeover sensor (optional)

YE

Electrical

heater