After pressing the travel calibration but-

ton (4), the actuator stem first moves as far

as it will go to the valve's CLOSED position.

Calibration is in progress when both signal

lamps (8 and 9) are lit.
Travel calibration starts after the mounting

position of the potentiometer gear (12) has

been determined automatically. This is indi-

cated by signal lamp (8) for 6 to 35 mm

travel and by signal lamp (9) for 6 to

19 mm travel.
When travel calibration starts, the lower sig-

nal lamp (9) blinks quickly for about 10 sec-

onds. The actuator stem retracts as far as it

will go (maximum travel - valve OPEN).
Travel calibration is successfully completed

when the end position is reached. The actu-

ator is in closed-loop operation. The actua-

tor stem moves to the valve position deter-

mined by the input signal.

NOTICE

If one of the signal lamps starts to blink

slowly after the travel calibration button has

been pressed and the actuator stem has ex-

tended to the valve's CLOSED position, the

potentiometer shaft (12.1) has been wrongly

positioned. Remount it manually.

Do not adjust the potentiometer before the

closed position is actually reached. This is

indicated by the associated, activated switch

on the board (Fig. 5 on page 13).

To proceed, adjust the shaft of the potenti-

ometer (12.1) by turning it gradually clock-

wise or counterclockwise with a screwdriver

until the signal lamp stops blinking and is

constantly illuminated. Turn the screwdriver

counterclockwise if the upper signal lamp (8)

blinks, and clockwise if the lower signal

lamp (9) blinks, corresponding to the icons

(7). Travel calibration does not continue until

both signal lamps are illuminated at the

same time.

NOTICE

If both signal lamps start to blink simulta-

neously during travel calibration, interrupt

calibration by pressing the travel calibration

button (4) and check the mounting position

of the potentiometer gear (12) again.

If no travel motion can be determined during

calibration, e.g. due to a loose or missing

potentiometer gear, both signal lamps blink

in alternating sequence.

If this is the case, interrupt travel calibration

by pressing the button (4), correct the fault,

and restart calibration by pressing the but-

ton (4) again.

16

EB 8331-1 EN