Design and principle of operation – Samson 3222/5757 User Manual

Page 8

Advertising
background image

2. Controllers with electric actuators

8

EB 5766 EN

Design and principle of operation

Type

5757

5724

5725

5757-7

5757

-10

-13

-20

-23

-10

-13

-20

-23

Nominal size

DN

15 to 25

15 to 25

15 to 25

32 to 50

15 to 25

32 to 50

Scope of application

Heating

DHW heating in instantaneous heating systems,

fixed set point control circuits in mechanical engineering

Safety function

Without

Without

With

Rated travel

mm

6

6

6

12

12

6

6

12

12

Transit time for rated travel

s

20

35

18

70

35

35

18

70

35

Transit time upon fail-safe
action

s

4

4

6

6

Fail-safe action

Stem extends

Nominal thrust

kN

0.3

0.7

0.5

Manual override

Yes

Yes

Possible

1)

Power supply

230 V (

±

10 %), 50 Hz

Power consumption approx. VA

3

3

3

7

3

7

5

9

5

9

Permissible temperatures

Ambient

°C

0 to 50

0 to 50

0 to 50

Storage

°C

–20 to 70

–20 to 70

–20 to 70

At connecting rod

°C

0 to 110

0 to130

0 to 130

Degree of protection

IP 42

IP 54 (upright position, acc. to DIN IEC 529)

Inputs and outputs of the digital controller

Temperature sensor Pt 1000

3 x

1 x

1 x

1 x

Setting range

°C

1 to 150

0 to 150

1 to 150

1 to 150

Potentiometer input

1000 to

1100/2000

Ω

Water flowmeter input

530 pulses/l

530 pulses/l

530 pulses/l

Current input

4 (0) to 20 mA

4 (0) to 20 mA

4 (0) to 20 mA

Binary input BE1

2)

Op. mode

switchover

Switching between internal set points/

Deactivation of function to maintain temperature constant

Binary input BE2

2)

Flow switch

Binary output BA

230 V/50 Hz

Cir. pump/Ex-
ternal demand

1)

Manual override using a 4 mm hex screwdriver (after removing the housing cover);
always returns to fail-safe position after safety release.

2)

Recommendation for Type 5724, Type 5725 and Type 5757: With gold contacts