9 appen dix 18, 1 wiring for type 5757-7 18, Appendix – Samson 3222/5757 User Manual

Page 18: Wiring for type 5757-7

Advertising
background image

9

Appendix

9.1

Wiring for Type 5757-7

(refer to EB 5757-7 EN)

Note!

The pump output L´ is non-floating (230 V~).

Note:

Terminals at point of installation, not included in scope of delivery

blk black · bl blue · br brown · gr green · or orange · rd red · ye yellow

Diagram abbreviations:
VS Flow sensor · RüS Return flow sensor · AS Outdoor sensor

18

EB 5766 EN

Appendix

or

ye

rd

br

blk

gr

br

bl

blk

3

4

6

5

2

1

L

N

230 V, 50 Hz

VS

Pt 1000

Pt 1000

Pt 1000

AS

RüS

Application with flow, return flow, and outdoor
sensors as well as binary input to switch between
operating modes = Default setting (WE)

Functions

WE

Configuration

Control w. reference variable 1

F01 - 1

Outdoor sensor

0

F02 - 0

Potentiometer/binary input

0

F05 - 0

BA as pump control output

0

F09 - 0

Return flow sensor

1

F11 - 1

or

ye

rd

br

blk

gr

br

bl

blk

3

4

6

5

2

1

L

N

230 V, 50 Hz

VS

Pt 1000

Pt 1000

AS

Application with flow sensor and outdoor sensor

Functions

WE

Configuration

Control w. reference variable

1

F01 - 1

Outdoor sensor

0

F02 - 0

BA as pump control output

0

F09 - 0

Advertising