7





C H A P T E R 3

Startup and Shutdown Procedure


Refer to the Installation Manual to secure the unit and install AC and DC wiring.

STARTUP PROCEDURE

For the initial startup of the system, follow the instructions in the Startup and Warranty

Validation Form. Failure to do so will void warranty.

CAUTION: HAZARDOUS VOLTAGES – ONLY QUALFIED SERVICE PERSONNEL SHOULD PERFORM

PROCEDURE.

1.

Verify that the installation switch located on the inverter chassis is in the OFF

position. Verify that AC input is disconnected.

2.

Press and hold the DC Pre-charge switch located on the inverter chassis for

approximately five seconds and then install the battery fuse. If a large flash

occurs, the batteries are not connected properly. Call service immediately.

3.

Energize the Mains AC input by turning on the units input circuit breaker and/or

the Distribution Panel breaker located upstream from the inverter.

4.

Turn the installation switch to the ON position. The Front Panel display should

now be illuminated and a slight hum should be heard from the inverter

transformer. The unit is now charging and the output should be energized.

SHUTDOWN PROCEDURE

1.

Interrupt the AC Mains to the machine by the Distribution Panel Breaker or the

machines input circuit breaker. The Inverter should then start.

2.

Turn the installation switch located on the inverter chassis to the off position. The

inverter should stop.

3.

Disconnect the main battery fuse located on the inverter chassis.

CAUTION: HAZARDOUS VOLTAGES STILL EXIST AT THE BATTERY TERMINAL

BLOCK AND WITHIN THE SYSTEM. AUTHORIZED SERVICE TECHNICIANS MUST

DISCHARGE DC CAPACITORS AND TURN OFF UTILITY POWER BEFORE

SERVICING EQUIPMENT.

CAUTION: DO NOT LEAVE THE SYSTEM SHUTDOWN FOR A PROLONGED LENGTH

OF TIME. LEAD BASED BATTERIES WILL EXPERIENCE PERMANENT DAMAGE

FROM LACK OF CHARGING AFTER A FEW MONTHS.