Gas connections, Check inlet gas supply – Lochinvar KNIGHT 51 User Manual

Page 48

Advertising
background image

48

Installation & Operation Manual

7

Gas connections

Nominal

Iron Pipe

Size (Inches)

Natural Gas Pipe Capacity Chart

Length of Pipe in Straight Feet for 1/2 PSI

10

20

30

40

50

60

70

80

90

100

125

150

175

200

1/2

175

120

97

82

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

3/4

369

256

205

174

155

141

128

121

113

106

95

86

79

74

1

697

477

384

328

292

267

246

236

210

200

179

164

149

138

1-1/4

1400

974

789

677

595

543

502

472

441

410

369

333

308

287

1-1/2

2150

1500

1210

1020

923

830

769

707

666

636

564

513

472

441

2

4100

2820

2260

1950

1720

1560

1440

1330

1250

1180

1100

974

871

820

2-1/2

6460

4460

3610

3100

2720

2460

2310

2100

2000

1900

1700

1540

1400

1300

3

11200

7900

6400

5400

4870

4410

4000

3800

3540

3330

3000

2720

2500

2340

4

23500 16100 13100 11100 10000

9000

8300

7690

7380

6870

6150

5640

5130

4720

Knight wall mount boilers are typically shipped ready to fire on natural gas. Check boiler rating plate to
determine which fuel the boiler is set for. If set to natural gas, it may be converted to LP by installing an orifice
(see page 13). In order to operate on LP gas, an orifice MUST BE installed. Failure to comply could result in
severe personal injury, death, or substantial property damage.

Table 7A Natural Gas Pipe Size Chart

The gas piping must be sized for the proper flow and length
of pipe, to avoid excessive pressure drop. Both the gas meter
and the gas regulator must be properly sized for the total gas
load.

If you experience a pressure drop greater than 1 inch w.c.,
the meter, regulator, or gas line is undersized or in need of
service. Perform the steps below when checking inlet gas
supply:

1.

Turn the main power switch to the “OFF” position.

2.

Shut off gas supply at the manual gas valve in the gas
piping to the appliance.

ƽ WARNING

3.

Loosen the set screw one (1) full turn from inside the
pressure tap on top of the gas valve. Place the tubing of
the manometer over the tap once the set screw is
loosened as shown in FIG. 7-3.

4.

Slowly turn on the gas supply at the field installed
manual gas valve.

5.

Turn the power switch to the “ON” position.

6.

Adjust the temperature set point on the control panel of
the SMART SYSTEM control module to call for heat.

7.

Observe the gas supply pressure as the burner fires at
100% of rated input. Percent of burner input will be
displayed on the control panel.

8.

Ensure inlet pressure is within specified range.
Minimum and maximum gas supply pressures are
specified in this section of the manual.

9.

If gas supply pressure is within normal range and no
adjustments are needed, proceed on to Step 11.

10. If the gas pressure is out of range, contact the gas utility,

gas supplier, qualified installer or service agency to
determine the necessary steps to provide proper gas
pressure to the control.

11. Turn the power switch to the “OFF” position.

12. Shut off the gas supply at the manual gas valve in the gas

piping to the appliance.

13. Remove the manometer from the pressure tap on top of

the gas valve. Re-tighten the set screw inside the pressure
tap.

Check inlet gas supply

NOTICE

CSA or UL listed flexible gas
connections are acceptable, but you
must exercise caution to ensure that the
line has adequate capacity to allow your
boiler to fire at full rate. Consult with
local codes for proper installation or
service procedures.

DO NOT adjust or attempt to measure
gas valve outlet pressure. The gas valve is
factory-set for the correct outlet
pressure. This setting is suitable for
natural gas and propane, requiring no
field adjustment. Attempting to alter or
measure the gas valve outlet pressure
could result in damage to the valve,
causing potential severe personal injury,
death, or substantial property damage.

ƽ WARNING