Troubleshooting – Lochinvar Copper-fin II/IIE Boiler User Manual

Page 41

Advertising
background image

3

Troubleshooting

(continued)

41

FAULT

DESCRIPTION

CORRECTIVE ACTION

Parameters

Progr

(Will require a manual

reset once the condition

has been corrected. Press

the RESET button on the
SMART SYSTEM

display

to reset.)

After downloading parameters from a laptop,
the main control board must be reset.

• Press the ENTER/RESET button on the Smart
System display panel.

Service Blk

While the unit is in Service Mode, the outlet
temperature has exceeded 185°F (85°C).

• Establish a heating load to remove heat from the
system.

• Verify that the system is full of water and that all air
has been properly purged from the system.

• Verify that the appliance is piped properly into the
system. Refer to the Water Connections Section of
the Installation and Operation Manual for the proper
piping methods.

• Check 120 VAC to the pump motor on a call for
heat. If voltage is not present, check the wiring
leading to the main control board. Replace the main
control board if necessary.

• If 120 VAC is present on a call for heat and the
pump is not operating, replace the pump.

Low Voltage

120 VAC input to the main control board has
dropped below 100 VAC.

• Check 120 VAC supply to the transformer.

• Check wiring connections at the low voltage terminal
strip.

• Check the wire size/length to remote devices.

• Replace the main control board.

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Operator Interface

Copper-fin II/IIE Boiler, Water Heater and Pool

Service Manual