Liebert 277 User Manual

Liebert Computer Accessories

Advertising
background image



Liebert AC Power Medium Exposure Transient Voltage Surge Suppressor, a surge protective
device designed with sine wave tracking to protect electronic equipment and microprocessor-based
systems from transients on distribution panels or any medium exposure locations.

Liebert Corporation • 1050 Dearborn Drive • PO Box 29186 • Columbus, OH 43229
Phone 607-724-2484 • Fax 607-722-8713 • US & Canada 800-288-6169
EMAIL: [email protected] • Web Site: www.Liebert.com

82246 Rev 0



















AC Power Medium Exposure TVSS Technical Specification

Connection Type................................................Parallel
Operating Voltage Range
.................................+/-15%
Fault Current Rating (AIC) ................................65 kAIC
Dimensions......................... (160 kA units) ......8”x6”x4”

.............................................. (100 kA units) ......6”x4”x3”

Operating Frequency Range............................47 – 63 Hz
Capacity ..............................................................Continuous
50 EMI/RFI Attenuation..................................40 dB
Response Time ..................................................<0.5 ns
Operating Humidity ...........................................0% to 95%
Operating Temperature.....................................-40º c to +50ºc
Dry Contact Rating ............................................
125vac, 8.0A, 1.0pf
Status Indication
................................................LEDs, Dry Contacts
Certifications ......................................................UL 1449, CUL, ISO 9001
Warranty..............................................................5 Years Parts

UL 1449 (second edition) Classification

120

volt

systems ................................ 400 volts all modes

208 and 277 volt systems ................. 800 volts all modes

480

volt

systems ................................ 1,500 volts all modes

100 kA

160 kA

ORDERING INFORMATION

Building A Model Number: LPM 1 2 3

1: Nominal Voltage Requirements

2: System Configuration

3: Surge Current Capacity

Nominal Voltage Requirements

Model ID

System Configuration

Model ID

L-N

L-L

L-G

120........ N/A........120 ............................120

Single (2 Wire + Gnd)

N or L

120 ....... 208 .......120 .................... .......120

Split (3 Wire + Gnd)

S

120........ 240........240 .................... .......120

Wye (4 Wire + Gnd)

Y

N/A........ 208........208 .................... .......208

Delta Hi-Leg (4 Wire + Gnd)

H

230........ 400........230 .................... .......230

Delta (3 Wire + Gnd)

D

N/A........ 240........240 .................... .......240

277........ 480........277 .................... .......277

N/A........ 400........400 .................... .......400

N/A........ 480........480 .................... .......480

Surge Current Capacity

Model ID

Surge Current Capacity

Model ID

160 kA/Phase ............................................160

100 kA/Phase .......................... 100 – 2

(L-N: 80 kA + L-G: 80 kA; N-G: 80 kA)

(L-N: 100 kA; N-G: 100 kA)

PANEL I.D.

MODEL NUMBER(S)

Job Name_______________________

Model# _________________________

Date ___________________________

Qty ____________________________

Quote# _________________________