History status, Figure 25 history status report screens, Figure 25 – Liebert Series 600T User Manual

Page 50: History status report screens

Advertising
background image

44

Operation

History Status

The History Status screen displays 64 frames, of 4 milliseconds each, from the Present Status screen. Note that
the values for output volts and amps are updated once each millisecond. Alarms are listed in the sequence they
occurred, within 1 millisecond resolution. The frames are stored in a buffer (a computer information storage
technique). The buffer stores the frames in a first-in first-out sequence. As a new frame enters the buffer the old-
est one is released.

When a designated fault occurs (see list below), the buffer stores information for the next 24 frames and then
freezes (stops gathering information). At that time, the History Status screen contains 40 frames before the fault,
the frame when the fault occurred, and 23 frames after the fault. This 64-page report is a very useful diagnostic
tool for the operator or Liebert Global Services. Use the Up and Down pads to view the screens.

Figure 25 History Status Report Screens

OUTPUT VOLTS
OUTPUT AMPS
OUTPUT FREQUENCY
LOAD KVA
BYPASS VOLTS

A

480
420

480

DC

B

480
420

480

TIME

LOAD

349

C

480
420

480

HERTZ

60.0

NEXT FRAME

PREVIOUS FRAME

EXIT

UP

:

DOWN :

SELECT :

HISTORY STATUS

MODULE-0

04/10/97

16:49:21

FRAME 36

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

**** ACTIVE ALARMS **** Output Ov-volts

OUTPUT VOLTS
OUTPUT AMPS
OUTPUT FREQUENCY
LOAD KVA
BYPASS VOLTS

A

380
530

380

DC

B

380
530

380

TIME

LOAD

349

C

380
530

380

HERTZ

50.0

NEXT FRAME

PREVIOUS FRAME

EXIT

UP

:

DOWN :

SELECT :

HISTORY STATUS

MODULE-0

04/10/97

16:49:21

FRAME 36

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

**** ACTIVE ALARMS **** Output Ov-volts

OUTPUT VOLTS
OUTPUT AMPS
OUTPUT FREQUENCY
OUTPUT VOLTS
OUTPUT AMPS
BATTERY VOLTS
OUTPUT VOLTS
OUPUT AMPS
BATTERY AMPS
INPUT VOLTS
INPUT AMPS
OUPUT VOLTS
OUTPUT AMPS
LOAD KVA

A

480
325

480
325

480
325

0
0

480
325

DC

390

-645

B

480
325

480
325

480
325

0
0

480
325

TIME

0:01

LOAD

270

C

480
325

480
325

480
325

0
0

480
325

HERTZ

60.0

NEXT FRAME

PREVIOUS FRAME

EXIT

UP

:

DOWN :

SELECT :

HISTORY STATUS

MODULE-0

01/17/98

11:21:59

FRAME 100

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

**** ACTIVE ALARMS **** Batt Discharging

Low Batt Warning

Advertising