Lennox Hearth ELITE VINT-DVS-U User Manual

Page 15

Advertising
background image

15

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

A

Flue Opening in the

top of the firebox

A

Restrictor

Restrictor

Installed Over

Flue Opening

Figure 23

Figure 25

Figure 24

Flue Restrictors

The flue restrictor settings shown in Figures 26 and 27 are for typical

installations and may need to be adjusted from standard to take into

account other variables in the installation to achieve proper combustion.

See Flue Restrictor Guidelines on this page to assist you in making a

proper flue restrictor adjustment.

This appliance uses balanced flue technology to ensure proper combus­

tion. A flue restrictor may need to be installed depending on the vent

configuration of your stove. The drawings on Page 16 show all the al­

lowable pipe configurations for this appliance. To properly install the flue

restrictor, find your pipe configuration in the drawings on Page 16 and

note which restrictor setting is recommended. The flue restrictor and two

black self­tapping 5/32” allen head screws can be found in the firebox

in a plastic bag. The restrictor should be placed over the flue opening

on the ceiling of the firebox. On the restrictor, two self­tapping 5/32”

allen head screws should be installed in either holes 1, 2, 3, or 4 in the

restrictor and screwed into the two holes in the firebox ceiling. See the

drawing to the right for the location of hole numbers on the restrictor. The

numbered holes in which the screws are inserted in the restrictor should

correspond to the restrictor position numbers found on the drawings for

your pipe configuration. Restrictor positions are based on tests run in

a laboratory. The optimum restrictor positions may need to be adjusted

slightly depending on the conditions surrounding the residential instal­

lation. Do not adjust restrictors to a point where the fireplace is sooting.

Notes: The higher the number of the flue restrictor position, the greater

amount of combustion air will be delivered.

Flue Restrictor Adjustment Guidelines

After the flue restrictors have been set to the standard settings as shown

in Figures 26 and 27 on Page 16, the burner flame appearance should be

evaluated to determined if the flue restrictors need to be set to a different

position to adjust for variables in your installation. Light the appliance

and allow it to burn for 20 minutes. See Flame Color and Behavior on

Page 21 to determine if you have a proper burner flame appearance. If

the proper flame appearance cannot be achieved, the flue restrictor may

need to be set to a different position. See the following guidelines to

determine if you need to readjust the flue restrictors.

Before proceeding, confirm the manifold and inlet gas pressure is correct,

primary air shutter is properly adjusted, venting system connections are

secure and not blocked and if you are at a high elevation, ensure unit has

been properly derated:

Symptoms - Lack of Combustion Air

If the symptoms listed below are present, you may need to adjust the

flue restrictor to a more open position.

• Flame appears yellow

• Floating Flames (lazy, ill defined, quiet, may roll)

• Sooting

• Pilot becomes yellow and appliance shuts down

Symptoms - Excessive Combustion Air

If the symptoms listed below are present, you may need to adjust the

flue restrictor to a more closed position.

• Low Flame

• Pilot pulls and appliance shuts down

• Pilot flame ghosts

4 3 2 1

Advertising
This manual is related to the following products: