Stove Installation

(for qualified installers only)

13

© Travis Industries

100-01177

4060802

Chimney Termination Requirements

Must have an approved cap (to prevent water from entering)

Must not be located where it will become plugged by snow or other material

Must terminate at least 3' above the roof and at least 2' above any portion of the roof within 10' (see
Figure 8)

Slanted Roofs

Flat Roofs

Chimney must
extend 3'
above the roof

Chimney must extend 2'
above any portion of the roof
within 10' of the chimney

Chimney must
extend 3'
above the roof

Chimney must extend 2'
above any portion of the roof
within 10' of the chimney

Figure 8

Outside Air Requirements

Required for mobile homes and in certain localities (check with building officials)

Must not be drawn from an enclosed space (garage, unventilated crawl space)

Requires 3” aluminum duct (do not use plastic “dryer-vent”) and a hose-clamp for securing to the
stove. Maximum 4’ length. NOTE: A 10’ length is allowed if using 4” diameter duct (use a 3” to 4”
converter).

If using the optional blower, you may need to “ovalize” the duct to route it under the blower box.

3” Air Duct (max. 4’ length)

A screen is required to prevent

rodents from entering.

Outside air entrance must be placed so it

does not become blocked by snow.

Air may be drawn from a ventilated crawl space.

Botttom of Stove

Use a hose clamp to secure the

aluminum air duct to the air inlet

flange on the stove.

Air Duct (3” Dia.)

Figure 9