Figure 2 capacity correction factor, Figure 3 pressure drop correction factor, Figure 2 – Liebert EMERSON 60 HZ User Manual

Page 9: Capacity correction factor, Figure 3, Pressure drop correction factor

Advertising
background image

5

Figure 2

Capacity correction factor

Figure 3

Pressure drop correction factor

Quiet-Line Models

040

6-12

4

1.4

7.4

1.5

11.4

1.6

17.0

1.7

23.5

12-24

8*

1.6

3.9

1.7

5.9

1.8

8.9

1.8

12.3

057

18-36

12*

2.1

3.6

2.2

6.1

2.3

8.6

2.3

11.9

24-48

16

2.2

3.0

2.3

4.6

2.3

6.2

2.4

8.6

060

12-24

8

2.2

7.1

2.3

11.3

2.4

16.6

2.5

23.0

24-48

16*

2.4

3.8

2.5

5.9

2.5

8.1

2.5

11.3

080

12-24

8

2.7

6.2

3.0

9.8

3.2

14.5

3.3

20.1

24-48

16*

3.2

3.3

3.4

5.1

3.6

7.0

3.7

9.7

111

24-48

16*

4.4

4.7

4.3

7.4

4.4

10.4

4.5

14.3

36-72

24

4.2

3.2

4.4

4.8

4.6

7.2

4.6

10.0

121

24-48

16*

4.4

6.1

4.7

9.7

4.8

13.7

4.9

18.9

48-96

32

4.8

2.9

4.9

4.9

5.0

7.0

5.1

9.6

158

24-48

16

5.6

6.4

6.0

10.3

6.3

14.7

6.6

20.3

36-72

24*

6.0

4.3

6.4

6.7

6.6

10.0

6.8

13.8

173

24-48

16

6.1

8.4

6.6

13.5

6.9

19.5

7.1

26.9

48-96

32*

6.9

4.1

7.2

6.8

7.4

9.7

7.5

13.5

178

24-48

16

6.5

12.3

6.9

20.0

7.1

29.1

7.3

40.1

48-96

32*

7.1

6.0

7.3

10.0

7.4

14.5

7.5

20.0

72-144

48

7.3

4.1

7.4

6.6

7.5

9.9

7.6

13.3

205

24-48

16

6.9

8.2

7.7

13.2

8.2

18.9

8.6

26.2

36-72

24*

7.8

5.5

8.4

8.7

8.8

12.9

9.0

17.6

248

24-48

16

7.6

10.7

8.5

17.4

9.1

25.2

9.4

34.8

48-96

32*

9.1

5.2

9.6

8.7

9.9

12.5

10.1

17.3

347

48-96

32

12.2

8.0

13.2

13.3

13.9

19.4

14.3

26.8

96-192

64*

13.8

4.1

14.4

6.7

14.8

9.7

15.0

13.4

356

48-96

32

12.9

11.9

13.8

19.8

14.3

29.0

14.5

40.0

96-192

64*

14.2

6.0

14.7

9.9

14.9

14.4

15.0

20.0

144-288

96

14.6

4.0

14.9

6.6

15.0

9.6

15.2

13.3

453

48-96

32

15.2

10.3

17.0

17.2

18.1

25.1

18.9

34.7

96-192

64*

18.2

5.2

19.2

8.7

19.9

12.5

20.3

17.3

498

48-96

32

16.1

15.4

17.8

25.6

18.8

37.6

19.2

51.8

96-192

64

18.8

7.7

19.5

12.8

19.9

18.6

20.1

25.7

144-288

96*

19.5

5.1

20.0

8.5

20.2

12.4

20.4

17.2

* Standard Circuiting
Based on 40% Ethylene Glycol Solution at 115°F average solution temperature expressed in MBH.
Specifications subject to change without notice.

Table 4

Drycooler performance data (continued)

Model

Number

GPM

Range

No. of

Circuits

MBH/°F Initial Temperature Difference

1.5 GPM/CIR

2.0 GPM/CIR

2.5 GPM/CIR

3.0 GPM/CIR

MBH/ITD PD ft. water MBH/ITD PD ft. water MBH/ITD PD ft. water MBH/ITD PD ft. water

Average Fluid Temperature

C

o

rr

ection

F

acto

r

Glycol % and average temperature °F

Average Fluid Temperature

Co

rre

ct

io

n Fa

ct

or

Glycol % and fluid temperature °F