READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE

This fixture is intended for installation in accordance with the National Electrical Code and local regulations. To

assure full compliance with local codes and regulations, check with your local electrical inspector before

installation. To prevent electric shock, turn off electricity at fuse box before proceeding.

Retain these instructions for maintenance reference.

INSTALLATION PROCEDURE FOR: 4X9 AND 9X9 MATRIX SERIES RECESSED

COMPACT FLUORESCENT EMERGENCY LIGHTING FRAME-IN KITS

INSTRUCTION SHEET NO.

IS:4X9EM

A0502

Page 1 of 4

A

COMPANY

631 Airport Road, Fall River, MA 02720

IMPORTANT SAFEGUARDS

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED INCLUDING:

1. Turn off AC power before proceeding.
2. Do not use outdoors.
3. Do not mount near gas or electrical heaters.
4. Do not attempt to service the battery. A sealed, rechargeable, no maintenance battery is used. Do not incinerate

or mutilate; may burst or release toxic materials. Do not short circuit; may cause burns. Battery acid can cause
burns to skin and eyes. If acid is spilled on skin or eyes, flush with fresh water and contact a physician
immediately.

5. Equipment should be mounted in locations and at a height where it will not be readily subject to tampering by

unauthorized personnel.

6. The use of accessory equipment is not recommended by the manufacturer and may cause an unsafe condition.
7. Do not use the equipment for other than intended use.
8. This unit has more than one power supply connection point. To reduce the risk of electrical shock, disconnect both

the normal and the emergency power supplies before servicing.

9. Before servicing to prevent electrical shock, disconnect the battery connectors on the emergency pack (location

on the end of the emergency pack). Make certain that the switch (if the fixture is switched) and the unswitched
lines to the emergency pack are turned off at the fuse box. Servicing should be performed by qualified personnel
only.

10. Be sure all electrical connections are complete before battery (inverter) connectors on emergency Pack are

connected.

11. The emergency battery pack must be fed from the same branch circuit as the AC ballast(s).
12. In switched fixtures, emergency pack must be connected ahead of any local switching.
13. Select the appropriate wiring diagrams to connect the emergency pack and the AC ballasts (see page 4).

SAVE THESE INSTRUCTIONS