Liebert Autochangeover Controllers AC4 User Manual

Product specification/installation sheet, Description, Features and benefits

Advertising
background image

1

AC4

Product Specification/Installation Sheet

Description

The Liebert AC4 is ideal for coordinated control of systems with

redundant equipment, such as multiple environmental units or

pumps. When the AC4 controller detects an alarm in an

operating device, the AC4 enables a standby device and controls

the device in alarm as configured, either leaving that device

operating or disabling it.
The AC4 controller can also balance usage of devices by rotating

units through Operating and Standby modes according to a user-defined schedule. This helps keep

redundant equipment operating efficiently and only when needed. The AC4 can perform routine

testing of standby devices and alert personnel if a standby device fails an operating test and

requires attention.
Another capability of the AC4 is monitoring the

status of connected devices and keeping

personnel apprised through local alarming.
The AC4 controller can interface with anything

that closes an electrical contact. To improve

process efficiency and troubleshooting, the

controller tracks data in two types of logs:

alarm and event. The AC4 has a local LCD

interface and an RS232 interface.
When an alarm condition arises, the AC4

displays alarm information, sounds an audible

alarm, changes the state of the common alarm

relay and turns connected devices on or off

according to user configuration.
For other applications, contact your local

Liebert representative or call 1-800-222-5877.

Features and Benefits

• Custom configuration for specific applications
• Alarm and Event logs with time and date

stamp

• Backup and download configuration files
• User interface for configuration and

monitoring via local LCD or RS232 port

• On-board audible alarm
• Configuration data and operating program

permanently stored in nonvolatile

Electrically Erasable Programmable Read

Only Memory (EEPROM) for protection

against power loss

• Real-time clock
• Status LEDs for verification and diagnostics

Digital output connectors

Digital input connectors

24VAC power connector

Digital output status LEDs

Digital output loss-of-power

jumper

Manual Override Switch

(outputs)

Status LEDs

Power On/Off switch

LCD connector

Digital input status LEDs

LCD contrast

adjustment

DIP switch 1

Common Alarm connectors

Audible horn

jumper

Audible horn

Serial interface connector

(RS232/EIA574)

AC4 Components and Key Features