21

3

General

venting

(continued)

Installation & Operation Manual

Table 3H Approved Stainless Steel (S.S.) Terminations and Adapters

The installer must use a specific vent starter
adapter at the flue collar connection,
supplied by the vent manufacturer to
adapt to its vent system. See Table 3H for
approved vent adapters. Discard CPVC
starter piece.

NOTICE

Approved Stainless Steel Vent Manufacturers

Make

Model

Dura Vent (M & G Group)

FasNSeal Vent / FasNSeal Flex* Vent

Z-Flex (Nova Flex Group)

Z-Vent

Heat Fab (Selkirk Corporation)

Saf-T Vent

Table 3G Stainless Steel Vent Pipe and Fittings

*Use of FasNSeal Flex smooth inner wall vent is to be used in vertical or near vertical sections only, taking precaution to ensure
no sagging occurs of the vent system. Connect to the FasNSeal rigid vent using specially designed adapters and sealing method,
see manufacturer’s instructions.

Stainless steel vent

This product has been approved for use with stainless steel
using the manufacturers listed in Table 3G.

Use only the materials, vent systems, and
terminations listed in Tables 3G and 3H.
DO NOT mix vent systems of different
types or manufacturers. Failure to comply
could result in severe personal injury,
death, or substantial property damage.

ƽ WARNING

Installations must comply with applicable
national, state, and local codes. Stainless
steel vent systems must be listed as a

UL-1738 approved system for the United
States and a ULC-S636 approved system
for Canada.

NOTICE

Installation of a stainless steel vent
system should adhere to the stainless
steel vent manufacturer’s installation
instructions supplied with the vent
system.

NOTICE

VENT

REPLACE APPLIANCE
SECURED CPVC ADAPTER
WITH APPROPRIATE
STAINLESS STEEL ADAPTER
FROM TABLE 3H

Figure 3-9 Near Boiler Stainless Steel Venting

Model

ProTech

Heat Fab

Z Flex

FasNSeal

Saf-T Vent

Z-Vent

Boiler

Adapter

Flue

Termination

Intake

Air

Termination

Boiler

Adapter

Flue

Termination

Intake

Air

Termination

Boiler

Adapter

Flue

Termination

Intake Air

Termination

55 - 85

303005

FSBS3

FSRC3(R.C)

303889

WH0002

9392

5300CI

9314TERM

2SVAKA02

2SVSTP03

2SVSRCX03

2SVSTEX0390

110 -285

303006

WH0003

2SVAKA03

399

303007

FSBS4

FSRC4(R.C)

FSAIH04

303888

WH0004

9492

5400CI

9414TERM

2SVAKA04

2SVSTP04

2SVSRCX04

2SVSTEX0490