Site planning data chart, Liebert upstation s™ site planning data, Mechanical data – Liebert UPStation S VM18000 User Manual

Page 5

Advertising
background image

5

Heat Rejection

at Full Load

BTU / HR

2170

2411

3616

4520

5062

7593

Weight

Including

Battery (lbs.)

270

270

560

560

560

780

Mechanical Data

Dimensions

in Inches

WxDxH

9x31x29

9x31x29

18x27x29

9x31x29

9x31x29

27x27x29

UPS Output

Circuit Breaker

(Amps)

30 A

30 A

100 A

100 A

100 A

125 A

Full Load

Currnet†Amps

23 A

22 A

21 A

20 A

19 A

25 A

25 A

25 A

25 A

25 A

40 A

39 A

36 A

35 A

33 A

50 A

48 A

46 A

44 A

42 A

60 A

58 A

55 A

52 A

50 A

90 A

87 A

82 A

78 A

75 A

AC Output

Voltage VAC

3-Wire +Ground

200/100

208/120

220/110, 220/127, 220 L-N

230/115

240.120, 240 L-N

200/100

208/120

220/110, 220/127, 220 L-N

230/115

240.120, 240 L-N

200/100

208/120

220/110, 220/127, 220 L-N

230/115

240.120, 240 L-N

200/100

208/120

220/110, 220/127, 220 L-N

230/115

240.120, 240 L-N

200/100

208/120

220/110, 220/127, 220 L-N

230/115

240.120, 240 L-N

200/100

208/120

220/110, 220/127, 220 L-N

230/115

240.120, 240 L-N

Battery

Internal Battery

Time Full / Half

Load¶ Minutes

12 /29

11 / 25

17 / 35

11 / 28

10 / 24

10 / 27

Recommende

d External

Overcurrent

Protection*

(Amps)

30 A

30 A

60 A*

60 A*

60 A*

50 A*

50 A*

70 A*

70 A*

70 A*

60 A*

60 A*

80 A

80 A

80 A

70 A

70 A

125 A

120 A

120 A

110 A

110 A

Full Load

Current †

Amps

22 A

21 A

20 A

19 A

18 A

24 A

24 A

22 A

21 A

20 A

36 A

35 A

33 A

31 A

30 A

45 A

43 A

41 A

39 A

38 A

50 A

49 A

46 A

44 A

42 A

76 A

72 A

69 A

66 A

63 A

AC Input

Voltage VAC

3-Wire + Ground §

200/100

208/120

220/110, 220/127, 220 L-N

230/115

240/120, 240 L-N

200/100

208/120

220/110, 220/127, 220 L-N

230/115

240/120, 240 L-N

200/100

208/120, 208/120 3 Ph. §

220/110, 220/127, 220 L-N

230/115

240/120, 240 L-N

200/100

208/120, 208/120 3 Ph. §

220/110, 220/127, 220 L-N

230/115

240/120, 240 L-N

200/100

208/120, 208/120 3 Ph. §

220/110, 220/127, 220 L-N

230/115

240/120, 240 L-N

200/100

208/120, 208/120 3 Ph. §

220/110, 220/127, 220 L-N

230/115

240/120, 240 L-N

Maximunm

Upgrade

Rating (kVA)

5.0

5.2

5.5

5.8

6.0

N/A

12.0

12.0

N/A

N/A

Power Rating

Power Rating

kVA/ kW

4.5 / 3.6

5.0 / 4.0

5.2 / 4.0

5.5 / 4.0

5.8 / 4.0

6.0 / 4.0

8.0 / 6.0

10.0 / 7.5

12.0 / 8.4

18.0 / 12.6

* For planned future upgrade, initially size wiring and overcurrent protection for future upgraded size.

¶ Extended run times available with optional external matching battery cabinets.

§ 8-18 kVA units accept optional 208V 3-phase 4-wire plus ground input. Full load current shown is based on UPS operation in bypass mode. In bypass mode, the UPS draws single phase current from the source, regardless of single or 3-phase input configuration.

† Full load current is the maximum amperage that each phase conductor can carry (L1-L2, L1-N, or L2-N), while not exceeding the total watt or kVA rating of the system.

Liebert UPStation S™ SITE PLANNING DATA