NEC Wire Gauge Chart

Allowable Ampacities of Insulated Conductors Rated 0 – 2000 Volts, 60° to 90°C (140° to 194°F), not more than three

conductors in Raceway or Cable or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)

*Unless otherwise specifically permitted elsewhere in this Code the overcurrent protection for conductor types marked with
an asterisk shall not exceed 15 amperes for No.14, 20 amperes for No.12, and 30 amperes for No.10 copper; or 15
amperes for No.12 and 25 amperes No. 10 aluminum and copper-clad aluminum after any correction factors for ambient
temperature and number of conductors have been applied.

Reprinted with permission from NFPA 70-1996, the National Electrical Code ®, Copyright 1995, National Fire Protection
Association, Quincy, MA 02269. This reprinted material is not the complete and official position of the National Fire
Protection Association on the referenced subject which is represented only by the standard in its entirety.

Size

Temperature Rating of Conductor

Size

60 C° (140°F)

75°C (167°F)

90°C (194°F)

60°C (140°F)

75°C (167°F)

90°C (194°F)

Types: TW*, UF*

Types: FEPW*,

RH*, RHW*,
THHW*, THW*,
THWN*, XHHW*,
USE*, ZW*

Types: TA, TBS,

SA, SIS, FEP*,

FEPB*, MI, RHH*,
RHW-2, THHN*,

THHW*, THW-2,

THWN-2, USE-2,
XHH, XHHW*,

XHHW-2, ZW-2

Types: TW*, UF*

Types: RH*,

RHW*, THHW*,
THW*, THWN*,
XHHW*, USE*

Types: TA, TBS,

SA, SIS, THHN*,

THHW*, THW-2,

THWN-2, RHH*,

RHW-2, USE-2,
XHH, XHHW*,

XHHW-2, ZW-2

AWG kcmll

Copper

Aluminum or Copper-Clad Aluminum

AWG kcmll

18

-

-

14

-

-

-

-

16

-

-

18

-

-

-

-

14

20*

20*

25*

-

-

-

-

12

25*

25*

30*

20*

20*

25*

12

10

30

35*

40*

25

30*

35*

10

8

40

50

55

30

40

45

8

6

55

65

75

40

50

60

6

4

70

85

95

55

65

75

4

3

85

100

110

65

75

85

3

2

95

115

130

75

90

100

2

1

110

130

150

85

100

115

1

1/0

125

150

170

100

120

135

1/0

2/0

145

175

195

115

135

150

2/0

3/0

165

200

225

130

155

175

3/0

4/0

195

230

260

150

180

205

4/0

250

215

255

290

170

205

230

250

300

240

285

320

190

230

255

300

350

260

310

350

210

250

280

350

400

280

335

280

225

270

305

400

500

320

380

430

260

310

350

500

600

355

420

475

285

340

385

600

700

385

460

520

310

275

420

700

750

400

475

535

320

385

435

750

800

410

490

555

330

395

450

800

900

435

520

585

355

425

480

900

1000

455

545

615

375

445

500

1000

1250

495

590

665

405

485

545

1250

1500

520

625

705

435

520

585

1500

1750

545

650

735

455

545

615

1750

2000

560

665

750

470

560

630

2000

CORRECTION FACTORS

Ambient Temp.

°C

For ambient temperatures other than 30° (86° F), multiply the allowable ampacities shown above by the appropriate factor shown

below.

Ambient Temp. °C

21-25

1.08

1.05

1.04

1.08

1.05

1.04

70-77

26-30

1.00

1.00

1.00

1.00

1.00

1.00

78-86

31-35

.91

.94

.96

.91

.94

.96

87-95

36-40

.82

.88

.91

.82

.88

.91

96-104

41-45

.71

.82

.87

.71

.82

.87

105-113

46-50

.58

.75

.82

.58

.75

.82

114-122

51-55

.41

.67

.76

.41

.67

.76

123-131

56-60

-

.58

.71

-

.58

.71

132-140

61-70

-

.33

.58

-

.33

.58

141-158

71-80

-

-

.41

-

-

.41

159-176