READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING LUMINAIRE

This luminaire is intended for installation in accordance with the National Electrical Code and local regulations.

To assure full compliance with local codes and regulations, check with your local electrical inspector before

installation. To prevent electric shock, turn off electricity at fuse box before proceeding.

Retain these instructions for maintenance reference.

IS:22UEM

INSTRUCTION SHEET NO.

C0312

Page 2 of 2

INSTRUCTION FOR INSTALLATION OF PRE-WIRED COMPACT FLUORESCENT

EMERGENCY LIGHTING DECORATIVE LUMINAIRES

INDICATOR

LIGHT

TEST

SWITCH

GREEN

TO LUMINAIRE AND

SUPPLY GROUND

HOT

(SWITCHED

OR

UNSWITCHED)

GRD

HOT

(UNSWITCHED

BLACK

EMERGENCY

BALLAST

AC

BALLAST

INVERTER

CONNECTOR

SKT

(COM) WHITE

WHITE

BLUE
BLUE

YELLOW

YELLOW/RED

YELLOW/RED

(COM) WHITE

WIRING DIAGRAM

OPERATION

When AC power is applied, the charge indicator light is illuminated indicating that the battery is being
charged . When the power fails, the emergency lighting ballast automatically switches to emergency
operation, keeping lamp illuminated at reduced output for 90 minutes.


MAINTENANCE


Although no routine maintenance is required to keep the emergency ballast functional, it should be
checked periodically to ensure that it is working. The following is recommended:

1. Visually inspect the charging indicator light monthly. It should be illuminated.
2. Test the emergency operation of the luminaire once every three months. Lamp should operate at

reduced output.

3. Conduct a 90 minute discharge test at least once a year or more if required by local ordinance. Lamp

should operate at reduced output for 90 minutes.

BLUE/RED

BLUE/RED

YELLOW

WHITE/BLACK

WHITE/RED

®