Chapter 1 introduction – Powerware Tie Cabinet Powerware 9355 User Manual

Page 7

Advertising
background image

EATON Powerware

®

9355 Tie Cabinet (20/30 kVA) Installation Guide

S 164201630 Rev A www.powerware.com

1

Chapter 1

Introduction

A Tie Cabinet can be installed as a wall-mounted bypass or to provide support for a
parallel system for redundancy or extra capacity.

A wall-mounted bypass switch is used to bypass the UPS during maintenance or
servicing, providing wrap-around bypass for UPS service without shutting down the
load.

A parallel (load sharing) system provides more capacity than a single UPS and can
provide backup, depending on the load and configuration. In addition, when one UPS
is taken out of service for maintenance or is not operating properly, a redundant UPS
continues to supply uninterrupted power to the critical load. A parallel Powerware

®

Hot Sync

®

Controller Area Network (CAN) Bridge Card provides connectivity for

system metering and operational mode control. The parallel system consists of two to
four UPSs, each with a parallel CAN Bridge Card and a parallel cabinet.

Figure 1 shows the Powerware 9355 UPS.

Figure 1. The Powerware 9355 UPS

Advertising