Control Panel Functions

NOTE Use this section only if the optional display is installed.

The EMS−UGK has a graphical LCD with backlight, four status LEDs, and
five control buttons (see Figure 18). The display provides useful
information about system events, measurements, and settings.

PRESS ANY KEY TO CONTINUE

Power On (green)

Overload (yellow)

No function (always off)

Alarm (red)

Control Buttons for the LCD Menu Options

Figure 18. EMS−UGK Display

The following table shows the indicator status and description.

Indicator

Status

Description

ON
Green

On

The product on which the EMS−UGK is installed is
operating normally.

Off

The product on which the EMS−UGK is installed is turned
off and will not turn on automatically.

O/L
Yellow

On

One or more phases is in overload, or there is an alarm or
warning for neutral overload, ground overload, main panel
breaker overload, or panel breaker overload.

OFF

Off

Not applicable for the EMS−UGK.

AL
Red

Flashing

There is a new or cleared EMS−UGK alarm condition. See

Troubleshooting" on page 61 for additional information.

To silence the horn, press any button.

On

An acknowledged alarm condition exists.