Battery Cabinet Installation

62

Powerware

®

FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide

:

Rev A www.powerware.com

NOTE If you have an external DC disconnect switch, see the instructions that came
with your disconnect switch.

Now, turn the DC ON/OFF switch on the battery cabinet(s) to
the ON position. Leave the UPS DC switch in the OFF position.

12. Use the meter to check for proper nominal DC voltage at the

UPS end of the cable. Make sure the polarity agrees with the
markings on the UPS battery terminals.

Table 29. Nominal Battery Voltage

Models

Nominal Battery

Voltage

QFE 500 VA, 700 VA, 850 VA, 1.15 kVA, and 1.4 kVA

12 Vdc

FE 500 VA, 700 VA, and 850 VA

24 Vdc

QFE 1.8 kVA, 2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA, and 7 kVA
FE 1.15 kVA, 1.4 kVA, 1.8 kVA, 2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA,
and 7 kVA

48 Vdc

FE and QFE 10 kVA, 12.5 kVA, and 18 kVA

120 Vdc

After you have checked the DC voltage, turn the DC switch on
the battery cabinet(s) to the OFF position.

13. Complete the phase check beginning on page 8.