UPS INSTALLATION PLAN AND UNPACKING

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

3−17

Table 3-15. Separate Rectifier Input Recommended Input Circuit Breaker Ratings

UPS Model

Input Rating for Each UPM

Load Rating

480V

Powerware 9395−825/650
Powerware 9395−825/750
Powerware 9395−825/825

80% Rated

500A

100% Rated

400A

C

A

U

T

I

O

N

To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current
ratings from Table 3-14 in accordance with the NEC, ANSI/NFPA 70.

The line-to-line unbalanced output capability of the UPS is limited only by the full load
per phase current values for AC output to critical load shown in Table 3-4 on
page 3−9
or Table 3-5 on page 3−10. The recommended line-to-line load unbalance is
50% or less.

Bypass and output overcurrent protection and bypass and output disconnect switches
are to be provided by the customer. Module Output Breakers (MOBs) are to be
provided by the customer. Table 3-16 lists the recommended rating for bypass,
output, and MOB circuit breakers.

Table 3-16. Recommended Bypass, Output, and MOB Circuit Breaker Ratings

UPS Model

Output Rating

Load Rating

400V

480V

Powerware 9395−825/650

80% Rated

1200A

1000A

100% Rated

1000A

800A

Powerware 9395−825/750

80% Rated

1600A

1200A

100% Rated

1200A

1000A

Powerware 9395−825/825

80% Rated

1600A

1600A

100% Rated

1200A

1000A