Operation/Service Section

Controls - Location, Operation, and Service

To service this system, it is necessary to understand the normal operation
of the controls and the function of the diagnostic circuit board. Refer to the
electrical box drawing in Figure 7 and to the individual illustrations to
identify and locate each of the controls. The wiring diagrams for this unit
are located in the main electrical box.

7. Electronic Circuit Board with Diagnostic

Lights

Location:

Control Compartment Electrical Box (See Figure 7)

Function:

The diagnostic lights on the circuit board are designed to assist

in troubleshooting. When the system is operating properly, the lights on
the circuit board are lit. If the system fails to operate properly, all lights on
the circuit board up to that one that represents the component or system
that has failed will be lit. For more detailed information, refer to the Trouble-
shooting Guide in Paragraph 19.

Figure 8 -
Diagnostic
Circuit
Board,
P/N 151263

Column of 13
indicator
bulbs; always
replace
burned out
bulbs, P/N
125189.

Figure 7 - Control Locations

8. Temperature Limit Safety Controls

Location:

1) Manual Reset Limit Switch is mounted on a 2x4

electrical box located in the blower section. To access the manual
reset, remove the blower section access panel to the left of the
discharge (left when facing the discharge); 2) Emergency Cutoff
Limit Control is in the burner/control cabinet just above the electri-
cal box.

• Manual Reset Limit Control - Blower
Cabinet

Function:

The

manual reset limit
is a temperature
activated safety
control. Re-start
of the system can
be done only after
the limit control is
cooled and the reset button is depressed.

CAUTION: If the manual reset limit activates,
find and correct the cause before re-starting the
system.

Service:

Failure of the manual reset limit requires replacement of

the control.

Figure 9 -
Manual Reset
Limit

Capillary tubing is

in a holder that

extends into the

Control

Relays

Outside Air Cutoff

(high ambient limit control)

Time Delay

Relay

24-volt Terminals

Ignition

Module

Maxitrol Amplifier

or Signal Conditioner

Service

Switches

Status Lights

Circuit

Board

24-V

olt

Terminals

Bypass

Damper

Motor

Return

Air

Damper

Motor

Motor

Starter

Transformer

Line Voltage

Terminals

Starter

Relay

Relay for

Optional 2-Speed

High

Low

Standard Pressure

Switches

Optional Bypass Damper

Pressure Switches

Optional

Dirty Filter

Pressure Switch

WARNING: Service work on this system
should only be done by a qualified gas ser-
vice person. The service information and
the troubleshooting guides are intended as
an aid to a qualified service person.

NOTE: Wiring diagrams for the unit are located on the inside of the electrical box door.