Wood consumption

Jøtul F

602 N has a nominal heat output of 7,0 kW. Use

of wood, with nominal heat emission: Approx. 2,3 kg/h.

Another important factor for proper fuel consumption is that the
logs are the correct size. The size of the logs should be:
Kindling:
Length: 30 - 40 cm
Diameter: 2 - 5 cm
Amount per fire: 8 - 10 pieces

Firewood (split logs):
Recomended length: 25 - 35 cm
Diameter: Approx. 8 - 12 cm
Intervals for adding wood: Approx. every 40 minutes
Size of the fire: 1,5 kg
Amount per load: 2 pieces

Nominal heat emission is achieved when the air vent is open
approximately 25%.

3.0 Installation

3.1 Floor

Foundations

It must be ensured that the foundations are dimensioned for
the fireplace. Cf. «2.0 Technical data» for specification of weight.
It is recommended that flooring which is not fastened to the
foundations – so-called floating flooring – is removed during
installation.

Requirements for protection of wooden
flooring

Jøtul F

602 N has a heat shield underneath which protects the

floor from radiation. The product can therefore be placed directly
on a wooden floor that is covered by a metal plate or other
suitable, non-inflammable material. The recommended minimum
thickness is 0,9 mm.
Any flooring made of combustible material, such as linoleum,
carpets, etc. must be removed from under the floor plate.

Requirement for protecting combustible
flooring in front of fireplace

The front plate must be in accordance with national laws and
regulations.

Contact your local building authorities regarding restrictions and
installation requirements.

3.2 Walls

Distance from the wall of flammable material
– cf. fig. 1

The fireplace is authorised for use with an uninsulated flue with
the distances to the wall of flammable material as shown in fig 1.

Distance to the flammable wall protected by
a firewall

Firewall requirement

The firewall must be at least 100 mm thick and be made of brick,
concrete-stone or light concrete. Other materials and structures
with satisfactory documentation may also be used.

3.3 Ceiling

Jøtul F

602 N may be assembled with the upper edge of the hot

air aperture min 1200 mm beneath the ceiling of the flammable
material.