Veris Industries H938 SERIES Datasheet User Manual

Current switches with relay: adjustable trip point, Status and control in one package, Typical coil performance

Advertising
background image

current monit

oring

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Status And Control In

One Package

DESCRIPTION

The Hawkeye Relay Combination Series is the ideal solution for the automation

installer. These units combine a current switch and relay into a single package,

reducing the space required for total control of fans and pumps. The current

switch and relay operate independently of one another. These devices allow

start/stop control and status monitoring with one device instead of two.

APPLICATIONS

Starting/stopping and monitoring positive status of motors

Detecting belt loss and coupling shear

FEATURES

Combines command relay and fan/pump status sensor in a single, easy to install

unit

Reduces number of components installed...fits better in small starter enclosures

Detect belt loss and motor failure...ideal for fan and pump status

H748 and H948 feature a SPDT command relay...control two outputs with a

single relay

Bracket on H938, H948, and H958 can be installed in three different

configurations...added flexibility

Reduced charges from electrician

Relay and status LEDs for easy setup

Polarity insensitive status output...fast and easy installation

Adjustable setpoint for current sensor status...fits many applications

5-year warranty

Maximize Reliability

Minimize Installed Cost

SPECIFICATIONS

Sensor Power

Induced from monitored conductor

Insulation Class

600VAC RMS

Frequency Range

50/60 Hz

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

Hysteresis

10% Typical

Terminal Block Wire Size

24-14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

Agency Approvals

UL 508 open device listing

Do not use the LED status indicators as evidence of applied voltage.

Current Switches with Relay:

Adjustable Trip Point

Year

Warranty

5

Voltage

AC

DC

24V................................... 10mA

10mA

12V.................................................................... 20mA

TYPICAL COIL PERFORMANCE

Hx38, Hx58 (SPST, N.O.)
Resistive
..................................10A@250VAC, 30VDC
Inductive.................................5A@250VAC, 30VDC

H735 (SPST, N.O.)
Resistive
..................................5A@250VAC, 30VDC
Inductive.................................3A@250VAC, 30VDC

RELAY CONTACT RATINGS

Hx48 (SPDT)
Resistive
.................................. 8A@250VAC, 30VDC
Inductive................................. 3.5A@250VAC, 30VDC

Pull In Voltage
Hx3x .............................................................. 20.1VDC
Hx48 .............................................................. 20.1VDC
Hx58 .............................................................. 8.4VDC
Drop Out Voltage
Hx3x .............................................................. 5.2VDC
Hx48 .............................................................. 5.2VDC
Hx58 .............................................................. 3.0VDC

H738

H938

H738 & H938 SERIES

TM

DETECTS BELT LOSS/COUPLING SHEAR!

DETECTS BELT LOSS/COUPLING SHEAR!

Now you can easily detect when drive belts slip, break, or pump couplings shear.

In fact, a typical HVAC motor that loses its load has a reduction of current draw

of up to 50%. That’s why our sensors are the industry standard for status.

Calibrated

Trip Point

Off

Off

Fan/pump

On

Loss of Belt/Coupling Shear

Electrical

Failure

HQ0001760.B 01131