Kt-mb-gtb-2ps, Technical data – VEGA KT-MB-GTB-2PS Compact PROFIBUS Power Hub User Manual

Page 2

Advertising
background image

2

Subject to reasonable modifications due to technical advances.

Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com

Technical data

KT-MB-GTB-2PS

R

e

le

ase

da

te

20

09

-0

4-

24

14

:53

D

ate

of

i

ssue

20

09

-0

4-

24

19

94

93-

0

007

_E

N

G.xm

l

Supply

Rated voltage

19.2 ... 35 V DC

Rated current

1.46 ... 0.77 A

Power loss

typ. 6.7 W

Fieldbus interface

Number of segments

2

Rated voltage

25 ... 28 V

Rated current

360 ... 10 mA

Short-circuit current

typ. 400 mA

PROFIBUS DP

Connection

Sub-D socket, 9-pin

Protocol

PROFIBUS DP/DP V1

Terminating resistor

100

Ω integrated

Indicators/operating means

LED ERR

red flashing: overload error at output

LED Seg 1...2

red 2 Hz flashing: PA error, red and LED DP/ERR red: MAU error

LED PWR

Power LED: green, if U

out

> 25 V

LED DP/ERR

red 2 Hz flashing: DP error ; red: Hardware error

Electrical isolation

CH/PROFIBUS DP

functional insulation acc. to IEC 62103, rated insulation voltage 50 V

rms

PROFIBUS DP/Supply

functional insulation acc. to IEC 62103, rated insulation voltage 50 V

rms

CH/CH

functional insulation acc. to IEC 62103, rated insulation voltage 50 V

rms

All circuits/FE

functional insulation acc. to IEC 62103, rated insulation voltage 50 V

rms

Fieldbus segment/Supply

functional insulation acc. to IEC 62103, rated insulation voltage 50 V

rms

Directive conformity

Electromagnetic compatibility

Directive 2004/108/EC

EN 61326-1:2006

Low voltage

Directive 73/23/EEC

EN 50178 (identical to EN 62103)

Standard conformity

Electrical isolation

IEC 62103

Electromagnetic compatibility

NE 21

Protection degree

IEC 60529

Fieldbus standard

IEC 61158-2

Shock resistance

EN 60068-2-27

Vibration resistance

EN 60068-2-6

Ambient conditions

Ambient temperature

-40 ... 60 °C (233 ... 333 K)

Storage temperature

-40 ... 85 °C (233 ... 358 K)

Relative humidity

< 95 % non-condensing

Shock resistance

15 g 11 ms

Vibration resistance

1 g , 10 ... 150 Hz

Mechanical specifications

Housing material

Polycarbonate

Housing width

see dimensions

Height of housing

see dimensions

Housing depth

see dimensions

Protection degree

IP20

Mass

approx. 0.9 kg

Mounting

DIN rail, system M36

Advertising