Maintenance, Reassembling – Liquid Controls Optical Air Eliminator US Patent 7000628 Refined Fuels Applications A8981 & A8981A User Manual

Page 13

Advertising
background image

13

Maintenance

Step 3

Place the plastic bonnet over the valve body and snap in

place.

Step 4

Place the coil over the armature guide post and fasten with

the thin hex nut. Tighten the nut with a 14mm wrench to a

torque of 4.5 in-lbs (0.5 Nm).

Reassembling

Step 1

Place the spring inside the plunger and insert the plunger,

spring end first, into the armature guide post. Place the ar-

mature guide post assembly on the valve body.
Fasten the armature guide post to the valve body using the

two screws removed earlier. Two holes of the valve body are

threaded and two are not. Make sure the screws are being

inserted into the threaded holes.
Note that the valve body has a number stamped into it. This

will be used to set the proper orientation of the solenoid

valve body with respect to the optical air eliminator housing

assembly.

Step 2

Align the solenoid valve body so that the stamped number on

the valve body faces the housing assembly as shown in the

picture to the left. The valve body can physically be fastened

to the housing assembly in one of two orientations. Only one

orientation is correct.

Number Stamp

Position solenoid valve body

with number stamp in this

location

IMPORTANT!

If the stamped numbers face away from the housing,

the optical air eliminator will not function properly. The

port will be blocked and the air eliminator will fail.

With the valve body in the proper orientation, fasten it to the

housing using the two screws removed earlier. Tighten to a

torque of 15 to 18 in-lbs (1.7 to 2.0 Nm).