INSTALLATION OF Model 272 TRANSMITTER

(Mounting, Protection)

Mounting: The Model 272 transmitter screws on and off of the flow meter. Because of the

random location of the starting point of the threads, one transmitter will probably not line up

with the “in” and “out” ports of the flow meter like another will. The electrical outlet of the

transmitter can be rotated clockwise or counter clockwise one turn by loosening the clamp-

ing screw at the base of the transmitter housing.

Two flats are provided for screwing the transmitter on to the flow meter. Care should be

taken when slipping the transmitter on and off. The wire of the stator is fine gauge and is

easily damaged.

Moisture Protection: The weather tight version of the transmitter has its electronic

circuitry enclosed in a liquid and vapor tight enclosure. All joints are sealed by welding or

by “O”-rings. If this sealed condition is to be maintained, the conduit connection to the

enclosure should be made liquid and vapor tight by using pipe dope or a potting fitting. If a

transmitter is located outside and this precaution is not taken, moisture may form inside the

housing. This will cause the circuitry to give an inaccurate output or possibly no output at

all. In the long run it will cause corrosion and failure. The amphenol connector 272 Models

offer moderate protection from moisture and dust, but are not totally sealed.

Temperature Considerations: High ambient temperatures (120°F/50°C) should be avoided if

possible. It is a good idea to locate the transmitter away from hot spots such as steam pipes,

ovens and heaters. The electronics of the 272 Series Transmitters are rated for operation up

to 65°C or 150°F. Because some heat travels from the flow meter to the transmitter

electrical enclosure, the temperature the electronics see is a function of both the

ambient and the flow meter temperature. Figure 3 shows the relationship between the

aximum ambient transmitter temperature and the fluid temperature through the flow meter.

Page 4

272-500-350 © 1996 (Rev. 8/00) Max Machinery, Inc.