Fire Fighting Enterprises FIRERAY 5000 4-Head (Legacy) User Manual
General information, En quick start guide, Wiring diagrams
1. General Information
• Check the beam spacing against
local regulations
• Position beam as high as possible,
but with a minimum distance of 0.5m
from Detector to ceiling
• Mount Detector and Reflector directly
opposite each other
• Do NOT position Detector where
personnel or objects can enter the
beam path
• Do NOT position 2 Detectors facing
each other
• LED indicator must face downward
18—50m = 1
50—100m = 4
8—18m = 1
Use Short
Range Mask
50cm
8-100m
50cm
Ensure clear line of
sight from Detector
to Reflector
Mount on solid surfaces (structural wall or
girder)
50cm
50cm
8-100m
Wiring for all other System Controllers (where more than one System
Controller is on one zone)
(Not to be used for UL region installations. Please refer to supplied CD for
UL region installation multiple-System Controller wiring)
Wiring for a single System Controller or last System
Controller on one zone
ZONE -
ZONE +
SUPPLY -
SUPPLY +
EARTH/SCREEN
Components not supplied (Check Fire Control Panel
manufacturer for values):
• Fire Resistor (Some Zone and Switch Interface Modules
do not need a Fire Resistor - replace Resistor with a
short circuit.)
• Detector Continuity Diode
• End Of Line (‘EOL’) component
• Check operation of Fire and Fault connection on Fire
Panel
• ALWAYS use a separate screened 2-core cable for
each detector head
• CAUTION: For system monitoring – Do not use
looped wire under any terminals. Break wire run to
provide monitoring of connections
Apply a
voltage of
5V to 40V to
‘Ext Reset’
contact for
at least 2
seconds to
clear a
Latched
Fire
condition
DET 1
DET 2
DET 3
DET 1
DET 2
DET 3
DET 4
14V - 28V DC
DET 4
14V - 28V DC
FIRE
ConA
1
2
3
N/O
Fire
Resistor
Fire
Resistor
Ext
Reset
Ext
Reset
EOL
COM N/C
N/O COM N/C
FAULT
ConB
1
2
3
FIRE
ConA
1
2
3
N/O COM N/C
N/O COM N/C
FAULT
ConB
1
2
3
EN
QUICK START GUIDE
Motorised Infrared
Optical Beam
Smoke Detector
2. Wiring Diagrams
Document Number: 0044-033-02-EN
• When ‘Set’ is displayed press
• When ‘S-00’ is displayed, cover the Reflector with a non-
reflective material and leave covered, then press
• When ‘S-01’ is displayed, uncover the Reflector and leave
uncovered, then press
• Repeat Steps 8 to 12 for any other Detectors found during
the ‘Find’ process
12. ‘Set’ 0/100 (Calibrate)
13. System is Aligned
• It is recommended to set the system back to ‘Lo A’ mode
• Green LED on Detector will flash every 10 seconds, and
Signal Strength should be between 99% and 101%
• Default values: 35% Fire Threshold, 10 second delay to
Fire and Fault, Non-Latching mode
• Refer to User Guide page 13-14 to change settings and
for Fire and Fault Test
14. Check Alignment Status Displays
A commissioned system
will display:
When Detectors have
been found but the
selected Detector is not
aligned the system will
display:
When a Detector is
connected but not
‘Found’ the system will
display:
European Approval Information
Complies with EN54-12 for sensitivity levels between 25%
and 35% with a maximum delay to fire of 20 seconds.
UL Approval Information
UL File Number: S3417
Distance between
Detector and Reflector
Fire Threshold
Range
8
—
10m (26.2
—
32.8ft)
10
—
18%
10
—
15m (32.8
—
49.2ft)
15
—
25%
15
—
22m (49.2
—
72.2ft)
15
—
35%
22
—
40m (72.2
—
131.2ft)
25
—
50%
40
—
60m (131.2
—
196.8ft)
35
—
50%
60
—
100m (196.8
—
328.1ft)
50%
All installations should comply with NFPA72
Approvals Information
Troubleshooting
E-01
Detector Not Found
System Controller could not find
Detector. Also displayed during
power up
• Wait 45 seconds for system to power up
• Check wiring between System Controller and
Detector (Voltage to Detector should be 11—13V)
E-02
Detector is connected but not
‘Found’
• Follow ‘Find’ process and align if necessary
E-08
Compensation Level Not Zero
Compensation must equal zero
when ‘Set’ is selected
• Re-align Detector using Auto-Align
E-09
Signal Strength Out of Range
Signal Strength is too low or too
high after Auto-Align
• Ensure correct distance has been set
• Ensure correct Reflector type has been used
• Ensure clear line of sight to Reflector
• Re-align Detector using LASER and Auto-Align
E-10
Reflector Not Found
Detector could not align with
Reflector
• Ensure correct distance has been set
• Ensure correct Reflector type has been used
• Ensure clear line of sight to Reflector
• Re-align Detector using LASER and Auto-Align
E-11
Auto-Align Failed
• Ensure correct distance between Reflector and
roof structures
• Ensure clear line of sight to Reflector
• Re-align Detector using Auto-Align
E-12
Cannot Zero During ‘S-00’ in
‘Set’
The Reflector was not covered or
the Detector was not aligned
onto the Reflector
• Ensure Reflector was completely covered with a
non-reflective material
• Re-align Detector using Auto-Align
E-13
No Signal During ‘S-01’ in ‘Set’
The Reflector was not uncovered
during ‘S-01’
• Ensure Reflector was uncovered when ‘S-01’ was
selected
E-14
‘Centre’ Stage of Alignment
Failed
Detector has aligned on some-
thing other than the Reflector
• Ensure clear line of sight from Detector to
Reflector for a radius of 0.5m