Lanair MXB400 User Manual

Page 33

Advertising
background image

Cleaning Suction Line Strainer

The suction line strainer should be cleaned every 30
days of operation. The element is a washable metal
element. If your waste oil is extremely dirty, this strainer
may need to be cleaned more frequently. Your vacuum
gauge will help you determine when the filter needs
cleaning. The vacuum gauge reading should not exceed
5" HG of vacuum. If it does, the strainer needs cleaning.

1. Disconnect power to the boiler.

2.

While holding the lower housing, unscrew the cen-
ter bolt on the top of the suction line strainer.

3. Rinse the filter and lower housing in solvent.

4. Air dry the strainer and lower housing.

5.

Re-assemble the strainer, ensuring the rubber gas-
kets, spring and o-rings are in place.

6. Fill the lower housing with waste oil or fuel oil.

7.

Position the lower housing to the top making sure
the o-ring is properly seated. Secure the top and
bottom together using the bolt, washer and gas-
ket removed earlier.

8.

Prime the fuel pump (see page 28).

Cleaning/Replacing Fuel Pump Strainer

1. Disconnect power to the boiler.

2. Remove four hex head screws from pump cover.

Carefully remove cover, strainer and gasket.

3. Clean housing, strainer and pump surface. Check

for excess wear.

4. Install a new gasket (P/N 9817).

5. Install strainer and pump housing.

6. Prime the fuel pump (see page 28).

Visit our website at: www.lanair.com

33

Section 18 - Service / Maintenance

bolt

washer

o-ring

inlet 1” NPT

outlet 1” NPT

strainer

strainer

hex cap screws

gasket

gasket

o-ring

spring

bowl

water drain

Advertising
This manual is related to the following products: