Vanguard VCBA ver.10.xx User Manual
Page 79
VCBA VERSION 10.xx SOFTWARE MANUAL
REV 2
77
8. Click on the “OK” button. The following window will be displayed:
9. You can select to initiate the trip command from this window. The following options are
available:
“Contact #1 Closed”: Trip breaker after detecting contact timing channel #1 is closed.
“No Delay”: Trip breaker with no delay. Both Close and Trip coils are energized at the
same time.
“Delay Between Close to Open in mS”: Trip the breaker with a preset delay between the
Close and Trip commands. This delay can be programmed from 10 ms to 500 ms in 1 ms
increments by typing the desired delay time in the corresponding input field.
Select the desired option by clicking on the corresponding radio box and then click on
the “OK” button. The following window will be displayed:
10. A 5-second timer will count down, and then the test will be initiated. A sequence of
status messages will be displayed, and when the test is complete, the tabulated results
will be displayed in the VCBA software main window. The test record will also be saved
to a file named TEMP001.DAT in the default test record directory.
NOTE
You can change the default test record directory. Please see section 3.4 for
further information.